0 the series dcp pressure module, Caution, 1 location – CAMCORP CAM-AIRO Vertical Cartridge User Manual

Page 29: Figure 1 switch connections, Master controller, Master controller input must not be connected

Advertising
background image

4-20 mA Connections

Receiver

Using DCT1000
24V Supply

Low
Limit

High
Limit

Pressure

Limit

Switches

+

-

Receiver

+

-

Optional Connection
Using External
Power Supply

+

Supply

-

Supply

Alarm

Load

4-20 mA
Connections

TB4

High
Limit

Com

Low

Limit

TB3

TB5

Alarm
Relay
Contacts

TB1

(Internally Connected)

Master Controller

(10 Channel Shown)

Com

Com

Alarm

Mode

Man

Ovr

Dt

Cln

Alarm

Reset

TB3

Daisy Chain

In Out

Daisy Chain

In Out

Master Controller
Input MUST NOT
Be Connected

To
Additional
Expander
Modules

(10 Channel Shown)

Slave Channel Expander

Line
Input

Solenoids

Sol

Com

L1 L2

1

2

3

4

5

6

7

8

9 10

Sol

Com

L1 L2

1

2

3

4

5

6

7

8

9 10

Line
Input

Solenoids

Normally Open Contacts

Current

Low Limit

High Limit

Next

Operation

Switch

Switch

Operation

Hold

Open

Open

Hold

Hold or Run

X

Closed

Run

Hold

Ø

Open

Hold

Hold

Closed

Ø

Run

Run

Closed

Run

Hold

Closed

Ø

Run

Run

Open

Hold

Ø Transition from open to closed

Transition closed to open

X Either open or closed

Note: If a DCP100 or DCP200 pressure module is installed
in the master controller, the switching functions on the previ-
ous page are ignored.

2.0 The Series DCP Pressure Module

The Series DCP100 or DCP200 Pressure Modules are
designed exclusively for use with the Dwyer DCT1000 Dust
Collection Board for on-demand cleaning requirements.
These series of modules are available in 10

w.c. [2.49 kPa]

or 20

w.c. [4.98 kPa] ranges, which allow for differential

process pressure measurement as indicated on the display
of the master controller. An isolated 4-20 mA readout chan-
nel is provided for remote pressure display. The 4-20 mA
output may be wired either for use with an external power
supply and indicator or using the isolated on-board 24 volt
power supply to power the loop.

Caution:

Prior to installing the DCP100/200 please

review the operating specifications carefully.
Some operating systems, especially in pneumatic

conveying applications, may see static pressure or vacuum
conditions that exceed the capability of the DCP100/200
pressure module. For these conditions there are a number of
alternate Dwyer pressure products that can be used to meet
your application requirements, all of which can be terminated
to the Dwyer DCT1000 dust collection timer board. For more
information on these and other Dwyer products, please call
us at (219) 879-8000, or visit us on the web at www.dwyer-
inst.com or www.dust-controls.com.

2.1 Location

The system should be located in an enclosure that meets rel-
evant safety standards and electrical codes. There are no
other special orientation requirements as the pressure mod-
ule is not orientation sensitive. Care should be observed

Figure 1

Switch Connections

3