Crestron chv-tstatrf infinet™ thermostat – Crestron electronic CHV-TSTATRF User Manual

Page 17

Advertising
background image

Crestron CHV-TSTATRF

infiNET™

Thermostat

CHV-TSTATRF in Heat-Cool Application with Integrated Control Unit

(Refer to “Basic Thermostat

Setup” on page 15)

Transformer

C

W

Y

G

R

Optional, for power

RH and RC jumpered
since control unit has
them on a single terminal

Heat

Relay

Fan

Relay

Cool

Relay

R

C

CHV-TSTATRF in Heat Pump System Application with Integrated Controller

RH and RC jumpered
since control unit has
them on a single terminal

Optional, for power

Transformer

R

C

C

Y

G

O

E - U - W

R

Compressor

Relay

Fan

Relay

Changeover

Valve

Aux Heat

Relay

(Refer to “Basic Thermostat

Setup” on page 15)

NOTE: Heat pump and dual-fuel heat pump systems require an outdoor temperature
sensor (e.g. Crestron’s C2N-RTHS, sold separately) to function properly. In SIMPL
Windows, connect the “Temp” output of the sensor to the “OutdoorTemp” input of
the CHV-TSTATRF. For details, refer to the SIMPL Windows help file. If using D3
Pro or SystemBuilder refer to “Programming with Crestron D3 Pro or
SystemBuilder” on page 30