Antifreeze added to boilers

must be non-toxic, and must be of a type specifically intended for use in closed

hydronic heating systems. Under no circumstances should automotive antifreeze be used. Antifreeze used

in any boiler may reduce capacity by 10% or more and increase fuel consumption. Tankless coil
performance will fall as concentration of antifreeze is increased. Refer to boiler and piping water volumes
tables in this manual.

BOILER WATER VOLUMES

PIPING WATER VOLUMES

Number of

Boiler Sections

Total Volume

(Gallons)

3

9.6

4

11.6

5

13.7

PIPE SIZE

COPPER PIPE

FACTOR

STEEL PIPE

FACTOR

82.5

63.5

%”

40.0

36.0

1”

23.3

22.2

1-1/4”

15.3

12.8

1-1/2”

10.8

9.5

2”

6.2

5.8

factor in table to determine volume in gallons.