Boiler with tankless coil, Sequence of operation – Kenmore 5EW1.75 User Manual

Page 34

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

SEQUENCE OF OPERATION

BOILER WITH TANKLESS COIL:

Aquastat high limit controller:

The aquastat control’s high limit contacts open and turn off the

burner when the boiler water temperature reaches the control’s

high limit set point. The high limit contacts automatically reset
after the boiler water temperature drops past the set point by 10°F,

which is a fixed'differential.

Aquastat low limit and circulator control:

With the adjustable differential at the minimum setting of 10°F;

On a boiler water temperature rise above the low limit set point,

the burner circuit contacts (RB) break and the circulator circuit

contacts (RW) make.

On a boiler water temperature drop of 10“F below the low limit

set point, the RB contacts make and the RW contacts break.

INTERNAL WIRING FOR HONEYWELL

AQUASTAT L8124C

With the adjustable differential setting greater than 10°F:

• When the boiler water temperature is at (or below) the low limit set point, the RB contacts make and fire the

burner and the RW contacts break leaving the circulator off. The burner will fire until the boiler water temperature

reaches the low limit set point plus the adjustable differential setting minus 10°F. At this point the RB contacts break
stopping the burner and the RW contacts make. With no call for space heating, operating in this way keeps the circulator
off and allows the boiler to give preference to the domestic water heating requirements.

Example: Consider the boiler

water temperature drops to 150°F with the low limit set at 160°F and the differential is set at 15°F. The burner will
begin to fire. When the aquastat probe senses a boiler water temperature of 165°F (15°F - 10°F

=

5°F, then 160°F

+5°F = 165°F) the RB contacts break and the RW contacts make.

When the boiler vrater temperature rises above the low limit / adjustable differential setting and the thermostat
controls call for domestic space heating. The sequence of operation for the burner and circulator is as follows:

1. Thermostat calls for heat, completing circuit between terminals T & T on the aquastat controller, energizing the IK relay

coil.

2. With the IK relay coil energized, contacts IKl and 1K2 are closed. Terminal B1 is energized, providing power to the oil

burner primary control. This, in turn, powers the ignition coil and burner motor.

3. With the primary control energized, the burner operation starts and remains running as long as the cad cell senses flame.

In the event of flame failure or the flame is not fully proven within the trial for ignition period, the primary control will
lockout and open the burner circuit. This will require a manual startup of the burner.

4. As long as flame is proven through the cad cell relay, the burner will remain on until the circuit is interrupted by the

boiler water temperature reaching the aquastat’s high limit setting (opening high limit contacts RB), or the thermostat is

satisfied breaking the T-T circuit.

5. Circulator pump is powered through terminal Cl and will run when boiler water temperature is above the low limit

setting and there is a call for heat from the thermostat. If the boiler water temperature reaches the aquastat’s high limit
setting and high limit contact RB is de-energized, the burner stops but the circulator pump will continue to run, as long

as, the thermostat calls for heat.

6. Whenever the boiler water temperature reaches the aquastat’s high limit setting, the high limit contact RB is de-energized

shutting the burner off. Then the boiler water temperature must fail 10°F below the aquastat’s high limit setting for the

high limit contacts RB to close and the burner to be energized.

7. When the thermostat is satisfied, the call for domestic space heating is ended. Relay coil IK is de-energized, opening

1KI and 1K2 contacts. Both the burner and circulator pump operation stop.

NOTE:

High limit setting must be a minimum of 20°F higher than the tow limit settinr