B. All Air from Outdoors: The confined space shall be provided with two permanent openings, one

commencing within 12 inches of the top and commencing within 12 inches of the bottom of the

enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces {crawl or
attic) that freely communicate with the outdoors.

1. When directly communicating with the outdoors, each opening shall have a minimum free area of

one square inch per 4,000 Btu per hour of total input rating of all equipment in the enclosure.

2. When communicating with the outdoors through vertical ducts, each opening shall have a minimum

free>area of one square inch per 4,000 Btu per hour of total input rating of all equipment in the

enclosure.

When communicating with the outdoors through horizontal ducts, each opening shall have a
minimum free area of one square inch per 2,000 Btu per hour of total input rating of all equipment in

the enclosure.

When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to

which they connect. The minimum dimension of rectangular air ducts shall be not less than three

inches.

3.

4.

f=RESH

AIR

DUCT

BOILER

FRESH AIR DUCT CAPACITIES FOR DUCTS SUPPLYING FRESH AIR TO BOILER IN TIGHTLY

CONSTRUCTED HOUSES

Fresh Air

Mesh Screen

Wood Louvers

Metal Louvers

Duct Size

(Btuh)*

(Btuh)*

(Btuh)*

3-'/2”x 12”

144,000

36,000

108,000

8” X 8”

256,000

64,000

192,000

8”x 12”

384,000

96,000

288,000

8”x 16”

512,000

128,000

384,000

*Btuh = British Thermal Units per hour based on opening covered by ‘/4” mesh

screen, wood louvers, or metal louvers.