Venting Through Roof - Clearances
#
0" clearance for 3" (or optional
2
") PVC, ABS, or CPVC Schedule
40 piping from combustible surfaces.
•
The Power Vent outlet terminal shall terminate at least 18" above
the roof surface. Figure 5.
#
The location selection must provide clearances for servicing and
proper operation of the water heater. Figure 4,
•
The venting system must be installed in a manner which allows
inspection of the installation of the venting pipes and joints as
well as periodic inspection after installation as required by ANSI
Standards.
■