Awarning, Installation instructions (cont’d), Venting (cont’d) – Kenmore 153.335963 User Manual

Page 17

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Installation Instructions (cont’d)

Venting (cont’d)

AWARNING

Be sure vent pipe is properly connected to prevent escape of

dangerous flue gases which could cause deadly asphyxiation.

AWARNING

Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium
and sodium chloride, waxes, bleach, and process chemicals are
typical compounds v^ich are potentially corrosive.

Vertical and horizontal runs must be securely supported at

3

V

2

VENTING THROUGH AN OUTSIDE WALL

ALL MODELS

3

"

ABS Schedule 40 vent piping supplied in the water heater

carton:

1. A3" ABS Schedule 40-45° vent cap with wire screen,

2.

A3"

PVC

Schedule

40-90°

street

ell;

used

to

connect

the

vent pipe to the water heater when the vent pipe is to be

turned norizontally directly ofF the blower.

3

.

A

5'

section of 3" PVC Schedule 40 pipe (more may be

required and must be supplied locally).

3" PVC SCHEDULE 40

90° ELBOW

S' SCHEDULE 40 PVC PIPE

VENT CAP

WITH SCREEN

The water heater requires its own (separate) venting system.

1. The water heater requires its own (separate) venting system.

2.

3" PVC, ABS or CPVC Schedule 40 piping and fittings are

acceptable

materials

for

the

vent

system

on

all

40

gallon

models and 50 gallon 40,000 BTU/HR models,

3 It cannot be connected to existing vent piping or chimney.

4. It must terminate horizontally to the outdoors.

ALL 40 GALLON AND 50 GALLON 40,000 BTU/HR

MODELS — OPTIONAL 2" VENT PIPING

2

" PVC Schedule 40 vent piping:

1.

A wire screen to fit a 2" PVC Schedule 40-45° vent cap is

supplied with the water heater.

2. A 2" PVC Schedule 40-45° vent cap (must be supplied locally).

3.

A 3" PVC Schedule 40 pipe, minimum length of 3" (must

be supplied locally).

4.

A

3"

to

2"

PVC

Schedule

40

reducer

(must

be

supplied

locally).

5.

A 2" PVC Schedule 40-90° street ell; used to connect the

vent pipe to the reducer when the vent pipe is to be turned

horizontally off the blower (supplied locally).

6. A 2” PVC Schedule 40 pipe (must be supplied locally).

r PVC SCHEDULE 40
90° ELBOW

(? 2" SCHEDULE ,0 PVC PIPE

a

3" TO 2" PVC REDUCER

ri

VENT CAP

AND SCREEN

3" SCHEDULE 40 PVC PIPE

(MINIMUM LENGTH 3")

1. The water heater requires its own (separate) venting system.

2.

2" and 3" PVC, ABS, or CPVC Schedule 40 piping and fit­

tings are acceptable material^ for the vent system on all 40

gallon and 50 g^lon 40,000 BTU/HR models.

3. It cannot be connected to existing vent piping or chimney.

4. It must terminate horizontally to the outdoors.

NOTE: See page 20 for vertical venting through a roof.

17

Advertising
This manual is related to the following products: