Eclipse Combustion AIRHEAT AH-MA User Manual

Page 15

Advertising
background image

Eclipse AH-MA Air Heat Burner v2, Design Guide 160, 8/1/05

15

Main

Gas

Gas Manifold

Burner

Feed Pipe

Pilot

Gas

Spark

Ignitor

Flame

Rod

Burner Body

Pilot End Plate

Plain

End Plate

Pipe

Union

Pipe

Union

Pipe

Union

Sizing and layout of the gas manifold
Choose the gas manifold size to evenly supply gas to each of the

sections, using Table 3.3 and Figure 3.2.

Table 3.3 Gas Pipe Sizing & Layout

Note:

Maximum inputs shown for natural gas only. For propane,

multiply inputs by 1.5; for butane, multiply inputs by 1.7.

Figure 3.2 Gas Manifold Sizing & Layout

Example: A gas manifold is supplying gas to two 1-1/2" N.P.T. rear

inlets on a burner. Each of the rear inlets supplies a maximum of

2,000,000 Btu/hr.
Solution: The total fuel supplied is 2 x 2,000,000 = 4,000,000 Btu/hr.
Referring to Table 3.3, the choice for manifold size is 2-1/2"; the

choice for main gas pipe size is 2".

MAXIMUM

MANIFOLD

MAXIMUM

MAIN GAS

GAS INPUT

PIPE SIZE

GAS INPUT

PIPE SIZE

(MMBTU/HR.)

(INCHES)

(MMBTU/HR.)

(INCHES)

1.4

1-1/2

0.3

1/2

2.5

2

0.63/4

5.2

2-1/2

1.1

1

8.0

3

3.2

1-1/2

14.0

4

6.6

2

45.0

613.0

2-1/2

80.0

8

20.0

3

Advertising