Eclipse AH-MA Air Heat Burner v2, Design Guide 160, 8/1/05

24

Figure 3.10 Staged Burner Valve Layout

Note:

A single pilot fuel feed can be used when the staged burners are

piloted by the adjacent burners.

Consult Eclipse
Eclipse can help you design and obtain a main gas shut-off valve train that

complies with the current safety standards.
The shut-off valve train must comply with local safety standards set by

authorities that have jurisdiction.
For details, please contact your local Eclipse representative or Eclipse

Combustion.

Note:

Eclipse supports NFPA regulations (two shut-off valves) as a

minimum standard for main gas “safety shut-off valves.”

Flexible

Nipple

Pipe

Union

Pipe

Union

Duct Wall

Flexible

Nipple

Flexible

Nipple

Pipe

Union

Main

Gas

(from shut-off

valve train)

Pilot

Gas

Main Gas

Control

Valve

Burner 1

Shut-Off Valve

Pilot

Pressure

Regulator

Solenoid

Valve

Manual

Butterfly

Valve

Main Gas

Control

Valve

Burner 2

Shut-Off Valve

Pilot

Shut-Off

Valve

Solenoid

Valve

Solenoid

Valve

Manual

Butterfly

Valve

Adjustable

Gas Cock

OR

Adjustable

Orifice Valve

& Gas Cock