Eclipse AH-MA Air Heat Burner v2, Design Guide 160, 8/1/05

20

Step 2:

Control

Methodology

The simplest control method is fuel modulation at fixed air flow. If

required turndown is greater than the burner’s capabilities, there

are two options:
1. Air Modulation

To lower the minimum input of the burner, the air flow can be

decreased as long as the pressure drop across the burner does not

go outside of the operating limits given in the “Operating Ranges”

chart in Data Sheet No. 160. The air flow can be changed with a

two-speed air handling system or a modulated system. As an

example, the air flow could be turned down from a pressure drop

of 1"w.c. to 0.25"w.c., giving a total air turndown of 2:1. This could

extend the minimum input level from 20,000 to 13,000 Btu/hr/ft.

Figure 3.8 Staged Burners

Staging

Divider Plate

Part No. 76506

Stage 2

Main

Gas

Stage 1

Pilot Gas

Pipe

Union

Pipe

Union

Stage 1

Main

Gas

Pipe

Union

Pipe

Union

Pipe

Union