Eclipse AH-MA Air Heat Burner v2, Design Guide 160, 8/1/05

23

Step 5:

Gas Valve Train

Selection

Figures 3.9 and 3.10 illustrate gas valve trains for single and staged

burner systems respectively.
The typical main gas valve train for a staged burner has the same valve

layout as a single burner except each burner has an individual sole-

noid valve to independently shut down each section. A common gas

shut-off valve train can be used.

Figure 3.9 Single-Staged Burner Valve Layout

Main Gas

Control

Valve

Main Burner

Shut-Off Valve

Pilot

Shut-Off

Valve

Pilot

Gas

Pilot

Pressure

Regulator

Solenoid

Valve

Adjustable

Gas Cock

OR

Adjustable

Orifice Valve

& Gas Cock

Manual

Butterfly

Valve

Main

Gas

(from shut-off

valve train)

Duct Wall

Flexible

Nipple

Pipe

Union

Flexible

Nipple

Pipe

Union