Wiring inputs and outputs

RTU Open Inputs and Outputs Table

Channel

Number

Type

Signal

Function

Part Number

Wire/Terminal

Numbers

Alternate

Terminals

Input 1

AI

4-20 mA

CO2
OAQ
Space Relative Humidity

33ZCT55CO2

33ZCT56CO2
33ZCSPTCO2 w/

33ZCASPCO2
33ZCSENSRH-02

J4

- 5 & 6

N/A

Input 2

AI

4-20 mA

CO2
OAQ
Space Relative Humidity

33ZCT55CO2

33ZCT56CO2
33ZCSPTCO2 w/

33ZCASPCO2
33ZCSENSRH-02

J4

-

2 & 3

N/A

Input 3

BI

24 Vac

Compressor Safety **
Fan Status
Filter Status
Remote Occupancy
Door Contact

N/A
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied

J1

-

2

J5

- 5 & 6

***

Input 4

BI

24 Vac

Safety Chain

*

N/A

J1

- 9

N/A

Input 5

BI

24 Vac

Fire Shutdown **
Fan Status
Filter Status
Remote Occupancy
Door Contact

Field-supplied
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied

J1

- 10

J5

- 3 & 4

***

Input 6

AI

10K

Thermistor

Supply Air Temperature

33ZCSENSAT

33ZCSENDAT

J2

- 1 & 2

N/A

Input 7

AI

10K

Thermistor

Outside Air Temperature

33ZCSENOAT

J2

- 3 & 2

N/A

Input 8

BI

24 Vac

Enthalpy **
Fan Status
Filter Status
Remote Occupancy
Door Contact

33SENTHSW
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied

J2

- 6 & 7

J5

- 1 & 2

***

Input 9

BI

24 Vac

Humidistat **
Fan Status
Filter Status
Remote Occupancy
Door Contact

--HL—38MG-029
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied

J5

- 7 & 8

N/A

Input 10

AI

10K

Thermistor

Space Temperature

33ZCT55SPT 33ZCT56SPT
33ZCT59SPT

J20

- 1 & 2

N/A

Input 11

AI

100K

Thermistor

Space Temperature
Setpoint Adjust

33ZCT56SPT 33ZCT59SPT

J20

- 3 & 4

N/A

Rnet

AI

Zone Temperature

SPS / SPPL / SPP

J13

- 1, 2, 3, 4

N/A

AO - 1

AO

Economizer

Economizer

Actuator-Field-supplied

J2

- 5 & 4

N/A

AO - 2

AO

N/A

Not used

N/A

J22

- 1 & 2

N/A

BO - 1

BO

N/A - Relay

Fan (G)

N/A

J1

- 4

N/A

Advertising