RTU Open

Effective Setpoints

The Effective Setpoints graph shows the current occupied or unoccupied setpoints. If occupied, these values are the current

programmed setpoints plus the offset of any setpoint adjustment that may be in effect. If unoccupied, the values are the

programmed unoccupied setpoints.

Point Name/Description

Default/Range

Heating –

(Occupied or Unoccupied, depending on mode) The current programmed Heating

setpoint adjusted by any offset that may be in effect.

R:

0 to 120°F

Cooling –

(Occupied or Unoccupied, depending on mode) The current programmed Cooling

setpoint adjusted by any offset that may be in effect.

R:

0 to 120°F

Optimal Start

– The number of hours prior to occupancy, at which the Optimal Start function

may begin to adjust the effective setpoints to achieve the occupied setpoints by the time

scheduled occupancy begins. Enter 0 to disable Optimal Start.

D:
R:

4 hr
0 to 4 hr

Occ Relative Humidity Setpoint

– The percentage of relative humidity in the space during

occupancy that will energize BO - 6 (Humidi-MiZer™).

D:
R:

60%rh
0 to Unoccupied

RH Control

Setpoint

Unocc Relative Humidity Setpoint

– The percentage of relative humidity in the space during the

unoccupied time period that starts the unit and energizes BO - 6 (Humidi-MiZer™).

D:
R:

95%
30 to 100%

DCV Max Ctrl Setpoint

– The design difference between indoor and outdoor CO2 levels.

D:
R:

650ppm
0 to 9999 ppm

Power Exhaust Setpoint

- The outside air damper position at which the controller energizes the

Power Exhaust relay. Configuration >Service Configuration > Economizer Exists must be set to

Yes

, and Configuration >Service Configuration > Continuous Occupied Exhaust must be set to

No

.

D:
R:

50% Open
20 to 90% Open