Appendix A: RTU Open Points/Properties

74

RTU Open

Point Name/Description

input 11

– Input Channel 11; 100K Potentiometer only. Setpoint adjust (T56, 59).

slidepot voltage reading

– Input Channel 11; used to detect an open circuit (faulty Setpoint adjustment mechanism).

input 3

– Input Channel 3; Dry Contact only. User-configurable for No Function, Compressor Safety, Fan Status, Filter

Status, Remote Occupancy, or Door Contact.
input 4

– Input Channel 4; Dry Contact only. Safety Chain.

input 5

– Input Channel 5; Dry Contact only. User-configurable for No Function, Fire Shutdown, Fan Status, Filter

Status, Remote Occupancy, or Door Contact.
input 8

– Input Channel 8; Dry Contact only. User-configurable for No Function, Enthalpy, Fan Status, Filter Status,

Remote Occupancy, or Door Contact.
input 9

– Input Channel 9; Dry Contact only. User-configurable for No Function, Humidistat, Fan Status, Filter Status,

Remote Occupancy, or Door Contact.
Sensor Invalid

– Reflects the status of the Space Temp (Rnet) input. On = Space Temp invalid,

Off = Space Temp valid.
ao 1

– Analog Output Channel 1; jumper selectable.

ao 2

– Analog Output Channel 2; 0 - 10 Vdc. Not Utilized.

relay 1

– Binary Output 1; Fan (G) Output.

relay 2

– Binary Output 2; Heat 2 (W2) Output.

relay 3

– Binary Output 3; Heat 1 (W1) Output.

relay 4

– Binary Output 4; Cool 2 (Y2) Output.

relay 5

– Binary Output 5; Cool 1 (Y1) Output.

relay 6

– Binary Output 6; Humidi-MiZer ™ Output.

relay 7

– Binary Output 7; Reversing Valve Output.

relay 8

– Binary Output 8; Power Exhaust Output.