RTU Open

55

If no heating or cooling is required or the current air source mode is satisfied, the VVT Master calculates the

weighted average of the occupied and unoccupied heating and cooling setpoints. It also calculates a zone

temperature that is midway between the setpoints (occupied or unoccupied based on the system’s current

occupancy status). This information, plus the occupancy status, is sent to the air source so that its current

mode is disabled and the unit ceases heating or cooling operation. If the system is occupied, the air source

fan and OA damper, if applicable, operate to maintain proper ventilation.

Linkage Air Source Modes

In a linked system, the air source determines its operating mode and qualifies that mode based on its own

Supply Air Temperature

(SAT). The following modes can be sent by the air source depending on its

configuration:

Off

– Air source fan is off

Fan Only

– Air source fan is on and providing ventilation (neutral SAT) without heating or cooling

Economizer Cooling

– Air source fan is on and providing cooling, using economizer only

Cooling

– Air source fan is on and cooling is provided by economizer and mechanical cooling

Heating

– Air source fan is on and heating is provided (gas or electric)

Dehumidification

– Air source fan is on and Humidi-MiZer™ is active

Test

– The RTU Open Service Test mode is active

Shutdown

– Air source fan is off due to Safety Chain, Fire Shutdown, or invalid SAT sensor

Unocc Free Cooling

– Air source fan is on, with the economizer providing cooling while unoccupied