RTU Open

39

Point Name/Description

Default/Range

Input 2 Function

– The type of sensor (4-20 mA) connected to terminals J4 – 1, 2, & 3.

D:
R:

No Sensor
No Sensor

IAQ Sensor

OAQ Sensor

Space RH Sensor

Input 3 Function

– The usage of Input 3. You must also set Input 3 Switch Configuration.

Options:

No Function

– The input is not used.

Compressor Safety

– Safety device status.

Fan Status

– Proves supply fan operation.

Filter Status

– Indicates a dirty filter.

Remote Occupancy

– Sets occupancy using a hardware contact.

Door Contact

– Disables mechanical cooling and electric or gas heating, when active.

D:
R:

Compressor Safety
No Function

Compressor Safety

Fan Status

Filter Status

Remote Occupancy

Door Contact

Input 3

Switch Configuration – The normal (de-energized) state for the set of contacts

terminated at Input

D:
R:

NO
NO/NC (normally

open/normally closed)

Input 5 Function

– The usage of Input 5. You must also set Input 5 Switch Configuration.

Options:

No Function

– The input is not used.

Fire Shutdown

– Fire Safety device status. Inhibits operation when tripped.

Fan Status

– Proves supply fan operation.

Filter Status

– Indicates a dirty filter.

Remote Occupancy

– Sets occupancy using a hardware contact.

Door Contact

– Disables mechanical cooling and electric or gas heating, when active.

D:
R:

Fire Shutdown
No Function

Fire Shutdown

Fan Status

Filter Status

Remote Occupancy

Door Contact

Input 5

Switch Configuration – The normal (de-energized) state for the set of contacts

terminated at Input

D:
R:

NC
NO/NC (normally

open/normally closed)

Input 8 Function

– The usage of Input 8. You must also set Input 8 Switch Configuration.

Options:

No Function

– The input is not used.

Enthalpy Switch

– Indicates enthalpy status (high or low).

Fan Status

– Proves supply fan operation.

Filter Status

– Indicates a dirty filter.

Remote Occupancy

– Sets occupancy using a hardware contact.

Door Contact

– Sets occupancy using a hardware contact.

D:
R:

Enthalpy Switch
No Function

Enthalpy Switch

Fan Status

Filter Status

Remote Occupancy

Door Contact

Input 8

Switch Configuration – The normal (de-energized) state for the set of contacts

terminated at Input

D:
R:

NO
NO/NC (normally

open/normally closed)

Input 9 Function

– The usage of Input 9. You must also set Input 9 Switch Configuration.

Options:

No Function

– The input is not used.

Humidistat

– Indicates high humidity condition.

Fan Status

– Proves supply fan operation.

Filter Status

– Indicates a dirty filter.

Remote Occupancy

– Sets occupancy using a hardware contact.

Door Contact

– Sets occupancy using a hardware contact.

D:
R:

Humidistat
No Function

Humidistat

Fan Status

Filter Status

Remote Occupancy

Door Contact