Carrier RTU OPEN 11-808-427-01 User Manual

Page 68

Advertising
background image

Appendix A: RTU Open Points/Properties

62

RTU Open

Point Name/Description

Default/Range

Input 5

Switch Configuration – The normal (de-energized) state for the set of contacts

terminated at Input

D:
R:

NC
NO/NC (normally

open/normally closed)

Input 8 Function

– The usage of Input 8. You must also set Input 8 Switch Configuration.

Options:

No Function

– The input is not used.

Enthalpy Switch

– Indicates enthalpy status (high or low).

Fan Status

– Proves supply fan operation.

Filter Status

– Indicates a dirty filter.

Remote Occupancy

– Sets occupancy using a hardware contact.

Door Contact

– Sets occupancy using a hardware contact.

D:
R:

Enthalpy Switch
No Function

Enthalpy Switch

Fan Status

Filter Status

Remote Occupancy

Door Contact

Input 8

Switch Configuration – The normal (de-energized) state for the set of contacts

terminated at Input

D:
R:

NO
NO/NC (normally

open/normally closed)

Input 9 Function

– The usage of Input 9. You must also set Input 9 Switch Configuration.

Options:

No Function

– The input is not used.

Humidistat

– Indicates high humidity condition.

Fan Status

– Proves supply fan operation.

Filter Status

– Indicates a dirty filter.

Remote Occupancy

– Sets occupancy using a hardware contact.

Door Contact

– Sets occupancy using a hardware contact.

D:
R:

Humidistat
No Function

Humidistat

Fan Status

Filter Status

Remote Occupancy

Door Contact

Input 9

Switch Configuration – The normal (de-energized) state for the set of contacts

terminated at Input

D:
R:

NO
NO/NC (normally

open/normally closed)

Space sensor type

- The type of local space temperature sensor.

D:
R:

T55
T55

T56 (Use for T59)

SPT Sensor

None

T5x Override Duration

– If using a T55, T56, or T59 sensor, this is the amount of time

that the controller runs in the occupied mode when a user presses the sensor's override

button for 1 to 10 seconds.

D:
R:

1 hr
0 to 24 hours

Sensor Calibration

Space Temp Calibration

– A calibration offset value to allow the local space temperature

sensor to be adjusted to match a calibrated standard measuring the temperature in the

same location.

D:
R:

0°F
-9.9 to 10°F

Supply Air Temp Calibration

– A calibration offset value to allow the supply air

temperature sensor to be adjusted to match a calibrated standard measuring the

temperature in the same location.

D:
R:

0°F
-9.9 to 10°F

Outside Air Temp Calibration

– A calibration offset value to allow the outside air

temperature sensor to be adjusted to match a calibrated standard measuring the

temperature in the same location.

D:
R:

0°F
-9.9 to 10°F