Continuous Occupied Exhaust

– Configures the exhaust fan control strategy (BO-8). If Yes,

the power exhaust runs continuously in occupied mode and is off in unoccupied mode. If

No

, the power exhaust is controlled by the Power Exhaust Setpoint.

D:
R:

No
No/Yes

Indoor CO2 Sensor Value @min (ma)

– The CO2 value that corresponds to a 4mA input at

the appropriate input channel.

D:
R:

0 ppm
0 to 9999 ppm

Indoor CO2 Sensor Value @max (ma)

– The CO2 value that corresponds to a 20mA input at

the appropriate input channel.

D:
R:

2000 ppm
0 to 9999 ppm

Outdoor CO2 Sensor Value @min (ma)

– The CO2 value that corresponds to a 4 mA input

at the appropriate input channel.

D:
R:

0 ppm
0 to 9999 ppm

Outdoor CO2 Sensor Value @max (ma)

– The CO2 value that corresponds to a 20 mA input

at the appropriate input channel.

D:
R:

2000 ppm
0 to 9999 ppm