Figure 2-5. removing terminal input block cover – Compaq R6000 Series User Manual

Page 36

Advertising
background image

Installation 2-11

Compaq Confidential – Need to Know Required

Writer: Dan Lyons Project: Compaq R6000 Series UPS Operation and Reference Guide Comments: revised as per A. May

Part Number: 347223-022 File Name: c-ch2.doc Last Saved On: 3/24/99 1:41 PM

NORMAL

BYPASS

138425244-001 REV

. P00

1
&
4

2

1

4

2

3

5

5

5

5

3

3

2

2

2

3

1

1

1

4

4

4

3

Figure 2-5. Removing terminal input block cover

3.

Remove the input wiring entry port cover.

4.

Pull the input wires through the conduit leading from the AC Mains,
leaving about 2 ft (0.5 m) of wire hanging from the end. Attach a
suitable connector to the end of the conduit.

5.

Feed the wires through the wiring entry port, the entry compartment and
the terminal input block compartment.

6.

Connect the conduit to the panel. Measure wires, cut and strip 0.5 inch
(1¼ cm) of insulation from the end of each incoming wire.

7.

Following the diagram on the input cover, connect the input wires to the
input terminal block connections and Ground. Ensure no loose strands
remain and that the terminal connection screws are tightened to torque
specifications found on the label immediately below the terminal block.

Advertising