LC-202W/LC-208W

Quick Start Guide

Figure 5: Floor Control Relay Connection

5.2.2

RS-485 Controller Network

All of the controllers in the elevator network communicate through an RS-485 serial
communication network. Per the RS-485 industry specification, this network must be daisy-
chained, with a total network cable length of no more than 4,000 feet. Make the RS-485 network
connections per the information in Table 2 and Figure 6 on page 12.

NOTE: Do NOT connect earth ground to the RS-485 network cable shield. The LC-200 controller
automatically connects earth ground to the shield at one point on the network. This single
connection minimizes the effects of ground loops that can affect controller performance.

Table 2: RS-485 Controller

Network

TB-1 Pin

Description

1

Tx/Rx Negative

2

Tx/Rx Positive

3

Network Cable Shield