Quick Start Guide

LC-202W/LC-208W

5.4

Wiring Multiple Panels Together

Up to 16 floors can be controlled using a combination of LC-202Ws and LC-208Ws; the first eight
floors must be controlled by an LC-208W. Any additional panel combinations of LC-208Ws and
LC-202Ws can then be used to reach the desired total.

5.4.1

LC-208W/LC-202W Combination

Perform the following wiring instructions to accommodate an elevator application using an LC-
208W and one or more LC-202W panels.

1. Make a complete set of connections to the LC-208W panel. Refer to Section 5.3 on page 16 for

all connections to the LC-208W.

2. Daisy-chain the Wiegand Data0, Ground, and Data1 reader connections from W-TB-B to the

LC-202W panels. Make the connections per the information in Table 7 and Figure 11 on
page 19.

3. Daisy-chain the RS-485 TxRx+, TxRx-, and Shield network communication connections from

the W-TB-B terminal strip on the LC-208W to each of the LC-202W panels. Make the
connections per the information in Table 8 and Figure 12 on page 20.

4. Refer to Section 5.2.4 on page 16 for the LC-202W panel power connections.
5. Refer to Section 5.2.1 on page 10 for the LC-202W floor relay connections.

Table 7: LC-208W W-TB-B to LC-202W Panel

W-TB-B

Connection

LC-202W TB-5/TB-6

Pin 1

Reader Common

Pin 1

Pin 2

Data0

Pin 4

Pin 3

Data1

Pin 7

Table 8: LC-208W to LC-202W Panel

RS-485 Network Communication Wiring

W-TB-B Connection LC-202W TB-1

Pin 4

TxRx-

Pin 1

Pin 5

TxRx+

Pin 2

Pin 6

Shield

Pin 3