All other reader connections to the remaining LC-202W panels are made per the following rules.

1. The reader data lines must be daisy-chained from the master elevator panel to all other elevator

panel data inputs – Data 0 to Pin 1 of TB-5 and TB-6 and Data 1 to Pin 7 of TB-5 and TB-6 on
the LC-202W panels.

2. The reader ground line must be daisy-chained from the master elevator panel to all other

elevator panel antenna grounds to provide a standard ground reference for all panels – Pin 4 of
TB-5 and TB-6 on the LC-202W panels.

Make the data line daisy-chain connections per the information in Table 5 and Figure 8 on page 15.

Table 4: Distribution Amplifier to

Master Elevator Panel

Amplifier WDA-TB-2 Panel TB-5

Pin 1

Pin 1

Pin 2

Pin 2

Pin 3

Pin 3

Pin 4

Pin 4

Pin 5

Pin 5

Pin 6

Pin 6

Pin 7

Pin 7

Table 5: Master Elevator Panel to Slave

Elevator Panels

Master Panel TB-5 Slave Panel TB-5 or TB-6

Pin 1

Pin 1

Pin 4

Pin 4

Pin 7

Pin 7