3 reader/amplifier daisy-chain, Wiegand elevator control panel – Keri Systems LC-208 Wiegand Elevator Control User Manual

Page 13

Advertising
background image

Wiegand Elevator Control Panel

1530 Old Oakland Road, Suite 100

01879-002 Rev. C

San Jose, CA 95112 USA
(800) 260-5265 (408) 451-2520 FAX (408) 441-0309
Web: http://www.kerisys.com E-mail: [email protected]

Page 13 of 24

LC-202W/LC-208W

Quick Start Guide

5.2.3

Reader/Amplifier Daisy-Chain

One Wiegand reader is shared by all elevator control panels in an elevator control application. The
Wiegand reader connections are made to the master LC-202W elevator panel, through a Wiegand
Distribution Amplifier (P/N 04197-001 – see Figure 7).

Figure 7: Wiegand Distribution Amplifier

Make the Wiegand reader to Distribution Amplifier connections per the information in Table 3
and Figure 8 on page 15.

Make the Distribution Amplifier to master elevator panel connections per the information in
Table 4 and Figure 8 on page 15.

Table 3: Wiegand Reader to Distribution

Amplifier

Reader

Amplifier WDA-TB-1

Data0

Pin 1

Beeper

Pin 2

Power

Pin 3

Ground and Cable Shield

Pin 4

Green LED (Dual)

Pin 5

Red LED (Single)

Pin 6

Data1

Pin 7