LAARS EBP 175 MBTU/h - Installation, Operation and Maintenance Instructions User Manual

Page 11

Advertising
background image

Endurance

Page 11

in the offset. All horizontal portions of the vent

system must slope a minimum 1/4" per foot toward

the condensate drip tee. Laars vertical vent kit and

individual venting components have condensate tees

that work in a vertical vent system, and therefore it

is not necessary to have an offset in a vertical vent

systems that use these parts.

The vertical vent terminal must be placed such

that the bottom of the vent cap is at least 2-feet (0.6m)

above any structure (such as the peak of a roof or

adjacent wall) within 10 feet (3.0m), and must be at

least 3 feet (0.9m) above where the vent pipe exits the

roof (

see Figure 12

).

Laars offers 3" vent parts for non-concentric

venting, including an in-line condensate tee and vent

caps for vertical venting. See

Figure 13

for 3" vent

parts, and

Figure 15

for an example of the inline

condensate in a vertical vent system.

IMPORTANT NOTE REGARDING ENDURANCE

VENTING: Regardless of the venting arrangement

being used, the flue gas vent material used with

the Endurance MUST be

stainless steel special

gas vent listed to U.L. Standard 1738 and U.L.C.

Standard 636. Endurance flue gases must

never

be vented into a masonry chimney or vented with

B-vent or other galvanized vent material. Endurance

units are

not permitted to be common vented with

any other appliance(s), including other Endurance

appliances.

2.3 Air Source For Combustion

(when not ducted to the Endurance)

When using Category IV venting methods the

appliance draws all combustion air through its top and

from the adjacent space. When locating the appliance

in unconfined spaces in buildings, infiltration may be

adequate to provide air for combustion and ventilation.

However, in buildings of unusually tight construction,

or when locating the appliance in a confined space,

additional air should be provided and the guidelines

below must be followed:

2.3.1 Air From Inside the Building

The following method shall be used to size the

air openings for boilers that are getting all of their

combustion air from inside the building.

The confined space shall be provided with two

permanent openings communicating directly with

other spaces of sufficient volume so that the combined

volume of all such spaces meets the criteria for an

unconfined space. The total input of all gas utilization

equipment installed in the combined spaces shall be

used to determine the required minimum volume.

Each opening shall have a minimum free area of not

less than 1 in.

2

/1000 Btu/hr (220 mm

2

/kW) of the total

input rating of all gas utilization equipment in the

confined space, but not less than 100 in.

2

(645 cm

2

).

One opening shall commence within 12 in. (30 cm) of

the top, and one opening shall commence within 12 in.

(30cm) of the bottom, of the enclosure. The minimum

dimension of air openings shall be not less than 3 in.

(8 cm).

2.3.2 All Air From Outdoors

When all air is provided from outdoors, but

not ducted directly to the Endurance, the following

methods shall be used to size the air opening(s).
a. Two permanent openings, one commencing

within 12 in. (30 cm) of the top and one

commencing within 12 in. (30 cm) of the bottom,

of the enclosure shall be provided. The openings

shall communicate directly, or by ducts, with

the outdoors or spaces (crawl or attic) that freely

communicate with the outdoors.

a1. Where directly communicating with the

outdoors or where communicating to the

outdoors through vertical ducts, each

opening shall have a minimum free area

of 1 in.

2

/4000 Btu/hr (550 mm

2

/kW) of

total input rating of all equipment in the

enclosure.

a2. Where communicating with the outdoors

through horizontal ducts, each opening

shall have a minimum free area of not less

than 1 in.

2

/2000 Btu/hr (1100 mm

2

/kW) of

total input rating of all equipment in the

enclosure.

b. One permanent opening, commencing within 12

in. (30 cm) of the top of the enclosure, shall be

permitted where the equipment has clearances

of at least 1 in. (2.5 cm) from the sides and back

and 6 in. (16 cm) from the front of the appliance.

The opening shall directly communicate with the

outdoors or shall communicate through a vertical

or horizontal duct to the outdoors or spaces that

freely communicate with the outdoors and shall

have a minimum free area of:

Minimum clearance from

combustibles (vent) U.S.*

3"

8cm

Minimum clearance from

combustibles (vent) Canada

6"

15cm

Max. flue gas temp.

325°F

163°C

Max vent pressure

1.5" w.c.

0.4kPa

Max. equivalent ft. of 3" venting (any

50

15

combination of horizontal or vertical)

equiv. feet equiv. meters

Max. equivalent ft. of 4" venting (any

100

30

combination of horizontal or vertical)

equiv. feet equiv. meters

*Note: To use 3" (8cm) clearance, the vent must be open on at least

one side. If fully enclosed, clearance is 6" (15cm)

Table 2. Category IV Vent Parameters.

Advertising
This manual is related to the following products: