LAARS Heating Systems

time. This is the length of time that the Endurance

pump will run after the call for heat has ended. It can

be used to purge heat from the boiler, putting it into the

system or transfer tank. It is adjustable from 0 to 10

minutes, and the default value is 3 minutes.

NOTE: Some systems are designed such that the

Endurance pump will be left with only the internal

recirculation path when a call for heat has ended.

Make sure the system design is known before setting

a pump time delay, so that the water has a path

during the purge time.

6.4.4 “Oar” Outdoor Reset

Outdoor reset can be turned on and off using the

“Oar” parameter. You must have an outdoor sensor,

properly located, to use this function.

IMPORTANT NOTE: The Endurance outdoor reset

is limited, to ensure that internal water temperature is

high enough to prevent heat exchanger condensation

and to keep the temperature of the water in the

20 gallon transfer tank high enough to serve the

domestic water plate heat exchanger at all times.

This feature is not meant to replace or mimic a

system outdoor reset controller.

6.4.5 “Oal” Minimum Outdoor

Reset Point

The “Oal” parameter tells the controller what

the minimum allowable supply temperature can be,

regardless of the outdoor reset calculation.

The default setting is 170°F (77°C) and it is

adjustable 170-200°F (77-93°C). The Endurance must

be able to keep the transfer tank at a high enough

temperature to generate the domestic water through the

DHW heat exchanger.

6.4.6 “rc” Outdoor Reset Ratio

The outdoor reset ratio is shown as “rc” in the

display. The ratio determines part of the relationship

between the outdoor temperature and the Endurance

supply temperature. It is adjustable between 0.1 and

5. The reset number represents the increase in the

Calculated Setpoint (CSP) for every degree below the

warm outdoor shutdown temperature.

The boiler control calculates CSP = Oal + (oTo –

air temp) x rc.

6.4.7 “oTo” Warm Outdoor Shutdown

When in the outdoor reset function is on, the

control has the ability to shut down the boiler system

when the outdoor temperature sensor reads the “oTo”

temperature that is set. This parameter is adjustable

from 55°-70°F (13°-21°C) and has a default setting of

65°F (18°C). The warm outdoor shutdown feature will,

not affect the generation of domestic water.

6.4.8 “unI” Temperature Units

The control has the ability to display and be

programmed in both °F (Fahrenheit) or °C (Celsius).

The “unl” lets the user choose between °F and °C.

6.4.9 “Dif” Burner On Differential

The differential between the Burner Control

Point and the Burner On Point is shown as “Dif” in the

display. If the Endurance reaches the Burner Off Point

Figure 33. Flow Schematic.