LAARS Heating Systems

the Anti-Condensing Valve (ACV) based on the

following boiler conditions:

ACV Open:

Heating system (T-T) call for heat, when

there is no tank charge or DHW call for

heat.

Cycles open and then closes every time the

Endurance is powered up.

ACV Closed:

Domestic hot water (DHW) call for heat.

Tank charge mode.

No heating system (T-T) call for heat.

6.6.8 Field-Supplied Outdoor Reset

Controls

When a stand-alone outdoor reset control is used

with the Endurance, it will only have the ability to

reset the system water temperature, and start/stop a

call for heat. Although this will work, be aware that

this will likely cut into the modulation range that the

boiler control is calculating, because the boiler control

is not changing its temperature settings. This may

result in an Endurance that works like an on/off boiler,

rather than the modulating boiler, and may cycle on

and off more frequently than desired.

Endurance units have built-in outdoor reset

capability, with the addition of the outdoor reset

sensor. This will reset the boiler supply temperature,

while ensuring that the temperature is not dropped

enough to affect the domestic water output, and

keeping the return temperature to the Endurance high

enough to prevent condensation on the heat exchanger.

IMPORTANT NOTE: The Endurance outdoor reset

is limited, to ensure that internal water temperature is

high enough to prevent heat exchanger condensation

and to keep the temperature of the water in the

20 gallon transfer tank high enough to serve the

domestic water plate heat exchanger at all times.

SECTION 7.

Boiler Start Up

7.1 Removal of Boiler From

Common Vent

NOTE: This section does not describe a method for

common venting Endurance boilers. It describes

what must be done when a unit is removed from a

common vent system. Endurance boilers are

not

permitted to be common vented with any other

appliance(s), including other Endurance appliances.

At the time of removal of an existing boiler, the

following steps shall be followed with each appliance

remaining connected to the common venting system

placed in operation, while the other appliances

remaining connected to the common venting system

are not in operation.

Button Action

Result

Up Arrow

Press for 1/2 second

1. Scrolls up through view menu

(Upper Right Button)

2. In setup menu, scrolls up through setup menu

3. In setup menu, after parameter is chosen, increases

the value of that parameter

Down Arrow

Press for 1/2 second

1. Scrolls down through view menu

(Lower Right Button)

2. In setup menu, scrolls down through setup menu

3. In setup menu, after parameter is chosen, decreases

the value of that parameter

Enter

Press and hold for 3 seconds

Puts the control is setup mode

(Lower Left Button)
Enter

Press for 1/2 second

1. When in setup view, chooses the parameter that the

(Lower Left Button)

user wants to adjust

2. When in setup menu, saves an adjusted parameter

Enter & Up Arrow Together

Press both together for 2 seconds

High fire hold for 5 minutes

(Lower Left and Upper

Right Buttons Together)
Enter & Down Arrow Together Press both together for 2 seconds

Low fire hold for 5 minutes

(Lower Left and Lower Right

Buttons Together)
Power

Press for 1/2 second

When in alarm mode, allows the user to scroll through

(Upper Left Button)

menu for 30 seconds

Power

Press and hold for 3 seconds

Turns control off or on to allow programming without a

(Upper Left Button)

call for heat interruption.

Table 4. Boiler Control Button Functions.