LAARS EBP 175 MBTU/h - Installation, Operation and Maintenance Instructions User Manual

Page 23

Advertising
background image

Endurance

Page 23

Figure 31. Control Logic Example.

off. If there is still a call for heat, it will energize

again when it reaches the Burner On Point. SP

default value is 190°F (88°C). It is adjustable from

170-210°F (77 - 99°C). SP has a fixed 10°F (6°C)

differential to the Burner Control Point. SP minus the

10°F (6°C) differential gives you the Burner Control

Point, which is the temperature the Endurance will

attempt to maintain, using its modulation features. The

differential between SP and the Burner On Point is

adjustable, using the Burner On Differential.

6.4.2 “PO” Pump Operation

This parameter, shown as “PO” in the selection

screen, allows the user to choose between the

Endurance pump running continuously (“Con”), or

running in the automatic mode (“Aut”) such that the

pump is energized only when there is a call for heat,

and has the option of a pump time delay when the call

for heat ends.

6.4.3 “Pd” Pump Delay

Pump delay is shown as “Pd” on the screen.

When pump operation “PO” parameter is set for

automatic (“Aut”), the user can choose the pump delay

6. Calculated Setpoint for Outdoor Reset (shown as

“CSP” – when used) – The temperature that the

controller has calculated for a setpoint, based on

the outdoor temperature, when outdoor reset is

being used.

6.4 Setpoint Menu

The setpoint menu is accessed by pressing the

enter button, and holding it for 3 seconds. Move

through the setpoint parameters by pressing the up and

down arrows. When the desired parameter is displayed,

press the enter button. Use the up and down arrows

to change the value of that parameter, and press enter

to save the change. Parameters that can be set on the

Endurance boilers are shown in the next sections.

The boiler control will automatically return to the

view mode if the control buttons are not pressed for 30

seconds.

6.4.1 “SP” Supply Temperature

Shown as “SP” in the control, the supply

temperature is the Burner Off Point. When the

temperature of the water that is leaving the boiler heat

exchanger reaches this setting, the Endurance shuts