4 locating the appliance, 5 clearances, Laars heating systems – LAARS EBP 175 MBTU/h - Installation, Operation and Maintenance Instructions User Manual

Page 4

Advertising
background image

Page 4

LAARS Heating Systems

Options Code

X = None

Revision

2 = Second

Revision

1.4 Locating the Appliance

The appliance is designed for installation on

combustible flooring, in alcoves, basements, closets,

or utility rooms. It must NOT be installed on

carpeting. IF INSTALLED IN A FINISHED AREA,

PROVISION SHOULD BE MADE FOR DRAINAGE

OF ANY ACCIDENTAL SPILLAGE OR LEAKAGE.

The location for the unit should be chosen with

regard to venting dimensions, convenient access to

piping, and accessibility for service and cleaning.

The boiler shall be installed so that the gas

ignition system components are protected from water

(dripping, spraying, rain, etc.) during appliance

operation or service (circulator replacement, control

replacement, etc.).

1.5 Clearances

The dimension and criteria in Table 1 should be

followed when choosing the location for the unit.

SECTION 2.

Venting Options

The Endurance boilers are certified as direct vent,

sealed combustion boilers, when vented using one of

the following two methods:
1) Concentric direct vent, which has a flue gas pipe

inside a combustion air pipe.

2) Non-concentric direct vent, using separate pipes

for the flue gases and the combustion air.

The Endurance boilers can also take air from the

space (when properly sized), and be vented as a

Category IV appliance.

The following sections describe the requirements

for each of these methods.

IMPORTANT NOTE REGARDING ENDURANCE

VENTING: Regardless of the venting arrangement

being used, the flue gas vent material used with

the Endurance MUST be stainless steel special

gas vent listed to U.L. Standard 1738 and U.L.C.

Standard 636. Endurance flue gases must never

be vented into a masonry chimney or vented

with B-vent or other galvanized vent material.

Endurance units are not permitted to be common

vented with any other appliance(s), including

other Endurance appliances.

Figure 3. Model Structure.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

E

B

P

I

F

2

X

Prod. Line

E = Endurance

Usage

B = Combination,

Heating &

Domestic

Water

Type

P = Standard

BTU Input

0 1 1 0
0 1 7 5

Fuel

N = Natural Gas

P = Propane

Altitude

A = 0' - 5,000'

H = Over 5,000'

Location

I = Indoor

Firing Mode

F = Modulating

Country of Sale

A = USA & Canada
R = Russia

Minimum Clearances From Combustible Materials

Back

1 inch

25mm

Left Side

1 inch

25mm

Right Side

1 inch

25mm

Front

1 inch

25mm

Top (Alcove Install)

1 inch

25mm

Top (Closet Install)*

22 inches 559mm

Vent: Concentric, Direct

0 inch

0mm

Vent: Category

3 inches

76mm

Suggested Serviceability Clearances

Front

18 inches 457mm

Left Side

6 inches 152mm

Right Side

6 inches 152mm

*Minimum closet height 6'9" 206 cm

Table 1. Clearances.

Advertising
This manual is related to the following products: