LAARS EBP 175 MBTU/h - Installation, Operation and Maintenance Instructions User Manual

Page 15

Advertising
background image

Endurance

Page 15

Figure 19. Hydronic Piping with Zone Valves.

Figure 20. Piping, Single Boiler for Multiple Temperature Systems.

providing flow for two heating zones (up to 67 feet

of ¾" baseboard each), and model 175 is capable of

providing flow for four heating zones (up to 67 feet of

¾" baseboard, each).

In radiant systems utilizing 3-way tempering

valves, a bypass pipe must be installed between supply

and return piping.

1. Connect system supply to 1¼" supply connection

marked “SUPPLY”.

2. Pipe the discharge of the relief valve, full size,

to a drain or in a manner to prevent injury in the

event of pressure relief.

3. Install an air purger in flow supply line as shown

in piping diagrams.

4. Install automatic float type air vent on air scoops.

5. Install a diaphragm expansion tank in boiler

outlet piping. To ensure sufficient expansion

volume for the hydronic system water, due to

heat-up and cool-down during normal operation,

a #30 or larger expansion tank must be used on

combo units.

NOTE: Never install expansion tank and auto fill

valve on return.

6. If necessary, install a properly sized circulator

with optional isolation valves in supply beyond

expansion tank.

Caution

To avoid the risk of fire which can result in

property damage, all hot water pipes must be

installed with a minimum 1" (25mm) clearance

from combustible materials.

7. Connect boiler feed water supply with shut off

valve to inlet connection of automatic fill valve.

Advertising