LAARS EBP 175 MBTU/h - Installation, Operation and Maintenance Instructions User Manual

Page 14

Advertising
background image

Page 14

LAARS Heating Systems

Figure 18. EBP Domestic Water Piping with Recirculating Loop.

appropriate water treatment.

WARNING

Failure to install a hot water tempering (mixing)

valve (12) creates a scalding hazard with potential

for serious bodily injury. Some brands of tempering

(mixing) valves are not designed as anti-scald valves.

Where domestic water is supplying multiple

apartments or large whirlpool tubs, an additional

storage tank may be connected as shown in

Figure

17

. The bronze circulator shown must be connected

to the tank aquastat and must not run continuously. If

the circulator is wired to run continuously, the unit’s

domestic water flow switch will keep the unit in

domestic water priority, and no water will be allowed

to be sent to the heating system.

Where domestic water is supplying a

recirculating loop, pipe per

Figure 18

. If the circulator

is wired to run continuously, the unit’s domestic

water flow switch will keep the unit in domestic

water priority, and no water will be sent to the heating

system. Wire the loop’s circulator through an aquastat

to maintain domestic water priority, while still

allowing the heating systems to function properly.

3.3 Anti-Freeze — Domestic Water

Endurance units use a flat plate heat exchanger

to heat domestic (potable) water indirectly. Endurance

units are equipped with a Low Temperature

control feature that recognizes when the boiler

water temperature (not the domestic/potable water

temperature) has fallen below 39° (4°C). If this

condition is recognized, the Endurance pump will run

for 5 minutes, or until the boiler water temperature

reaches 45°F (7°C). If the boiler water temperature

remains below 45°F (7°C) for 5 minutes, the appliance

will start its ignition sequence, in hopes of firing, and

heating the boiler water. The display will show [ICE]

during this time.

This feature is intended to assist in protecting

the boiler from freezing conditions, and does not

help to protect any other part of the boiler or water

heater system. This feature will not help to protect the

domestic (potable) water in the system from freezing

conditions.

SECTION 4.

Hydronic Heat Piping

4.1 Hydronic Piping

The appliance incorporates its own circulating

pump and bypass loop and is capable of providing

flow through heating zones, in addition to what

it needs for itself. Model size 110 is capable of

Caution

Power outage, interruption of gas supply, failure

of system components, activation of safety

devices, etc., may prevent a heater from firing.

Any time a heater is subjected to freezing

conditions, and the heater is not able to

fire, and/or the water is not able to circulate,

there is a risk of freezing in the heater or in

the pipes in the system. When water freezes,

it expands. This can result in bursting of pipes

in the system, or damage to the heater, which

could result in leaking or flooding conditions.