LAARS HEATING SYSTEMS

Page 14

OPTIONAL PUMP MOUNTED UNIT AVALIABLE

BOILER CIRC.
PUMP

COLD WATER

MAKE-UP

SYSTEM PUMP

SYSTEM

RETURN

SYSTEM

SUPPLY

C

THERMOMETER

GLOBE VALVE

CHECK VALVE

PRESSURE REDUCING VALVE
W/ FAST FILL BYPASS

EXPANSION TANK
WITH AIR SCOOP AND
AUTO AIR VENT

PUMP

LEGEND

VALVE

TEMPERATURE
SENSOR

3-WAY VALVE

PURGE
VALVE

INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM
PIPING & SIZING OF EXPANSION TANK
PER TANK MANUFACTURER'S INSTRUCTIONS

PRIMARY/SECONDARY MANDITORY FOR ALL
VARIABLE FLOW SYSTEMS

BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER

BOILER CIRC. PUMP TO BE USED WITH EM

DOTTED DEVICES INDICATE ALTERNATE LOCATIONS

BOILER CIRCUIT PIPING MUST BE EQUAL TO
BOILER WATER CONNECTION SIZE

SYSTEM TEMP. INTERLOCK REQUIRED

MULTIPLE STAGE BOILERS RECOMMENDED

PUT BOILER CONTROL SENSOR IN THE OUTLET

WHEN USING THIS PIPING STYLE

2

CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING. CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.

DIMENSION ''C'' TO BE 4 PIPE DIAMETERS
DIMENSION ''D'' TO BE 18" MINIMUM

D

Figure 24. Hydronic Piping - Primary-Secondary, Reverse-Return.