LAARS Mighty Therm HH-PH (Sizes 175-400) - Installation, Operation and Maintenance Instructions User Manual

Page 7

Advertising
background image

Mighty Therm HH-PH Hydronic Boilers

Page 7

NOTE: Check with louver manufacturers for net

free area of louvers. If not available, add 50 percent

for each screen/louver to the net free area. Check all

local codes applicable to combustion air.

2D-1. Outdoor Air Supply
When combustion air comes directly through an

outside wall, each opening must have a minimum free

area of at least one square inch for each 4,000 BTU/h

input of the total input rating of all appliances in the

enclosed area. (In Canada, refer to CGA B149.1

and .2.)

2D-2. Indoor Air Supply
Confined and non-confined areas have different

requirements for installation. Consult the latest edition

of the National Gas Code for installation requirements.

2D-3. Exhaust Fans or Vents
Any equipment which uses air or removes air

from the boiler room can use up the combustion air

supply or reverse the natural draft action of the

venting system. This could cause flue products to

build up in the boiler room. More air must be supplied

to make up for the decrease. This must be designed by

a qualified engineer.

2E. Venting of Combustion Products

2E-1. General Information
When installed indoors, the drafthood and the

vent damper device (models 175 and 250) must be

connected to a venting system without alteration. The

venting system must be installed by a qualified

installer and in accordance with the latest edition of

ANSI Z223.1. In Canada, the installation must be in

accordance with CAN1-B149.1 or .2, and any local

codes that apply.

The vent pipe must have a listed vent cap and

extend at least 2 feet (0.6 m) above any object within a

10 foot (3.0 m) radius (see Figure 15).

Figure 14. Typical Roof Mounting.

Required Net Free Opening Area

Directly from Outside

At Top

At Bottom

Model

in.

2

cm

2

in.

2

cm

2

175

44

284

44

284

250

63

406

63

406

325

82

529

82

529

400

100

645

100

645

Note: For screens or louvers, add 50%.

Table 2. Air Openings to Outside.

Figure 15. Indoor Installation Venting.

Notes:
1.

The drafthood must sit directly on top of the boiler
as shown and must not be altered in any manner.

2.

An Underwriters' Laboratories listed vent cap is
required to eliminate downdraft and allow the
boiler to function properly.

3.

Use approved roof fitting.

4.

Vent damper is required on models 175 and 250.

2D. Combustion and Ventilation

Air Supply

All indoor installations must have openings to

outside air for combustion, ventilation and dilution of

flue gases from inside the building (see Figure 15 and

Table 2). Laars does not recommend indoor

installations that do not provide combustion air from

outside the building.

Boiler rooms which are confined spaces require

two permanent air supply openings: one within

12 inches (305 mm) of the ceiling, the other within 12

inches (305 mm) of the floor.

Advertising