LAARS Mighty Therm HH-PH (Sizes 175-400) - Installation, Operation and Maintenance Instructions User Manual

Page 8

Advertising
background image

LAARS HEATING SYSTEMS

Page 8

NOTE: Do not use sheet metal screws at the

snap lock joints of Type B gas vents.

Do not weld or bolt the vent pipe to the boiler

drafthood or the vent damper if one is installed. The

weight of the stack must not rest on the boiler. The

drafthood and boiler top must be easily removable for

normal boiler service and inspection.

WARNING

Avoid ending boiler vents near air conditioning or air
supply fans. The fans can pick up exhaust flue
products from the boiler and return them inside the
building, creating a possible health hazard.

Avoid horizontal runs of the vent pipe, and 90

degree elbows, reductions and restrictions. Horizontal

runs should have at least a ¼ inch (6 mm) rise per foot

in the direction of flow. Support a vent connector for

the design and weight of the material used to maintain

clearances and prevent physical damage and

separation of joints.

Always use double-wall or insulated vent pipe

(Type B or equivalent).

WARNING

In cold weather, uninsulated outside vents can chill
the rising flue products, blocking the natural draft
action of the venting system. This can create a
health hazard by spilling flue products into the boiler
room.

Avoid oversize vent piping or extremely long

runs of the pipe which may cause too much cooling

and condensation of flue gasses.

2E-2. Replacement of Existing Boiler
At the time of the removal of an existing boiler,

the following steps shall be followed with each

appliance remaining connected to the common venting

system. During the testing of each unit, the other

appliances remaining connected to the common

venting system should not be operated.
1.

Seal any unused openings in the common

venting system.

2.

Visually inspect the venting system for proper

size and horizontal pitch. Determine that there is

no blockage or restriction, leakage, corrosion, or

other deficiencies which could cause an unsafe

condition.

3.

As far as possible, close all building doors and

windows. Also close all doors between the space

in which the appliances remaining connected to

the common venting system are located and the

other spaces of the building. Turn on any clothes

dryer and any appliance not connected to the

common venting system. Turn on any exhaust

fans, including range hoods and bathroom

exhausts, so they will operate at maximum

speed. Do not operate a summer exhaust fan.

Close all fireplace dampers.

4.

Place in operation the appliance being inspected.

Follow the lighting instructions for the unit.

Adjust the thermostat so the appliance will

operate continuously.

5.

After 5 minutes of main burner operation, test for

spillage at the draft hood relief opening. Use the

flame of a match or candle, or smoke from a

cigarette, cigar, or pipe.

6.

The tests should show that each appliance

connected to the common venting system vents

properly. Return all doors, windows, exhaust

fans, fireplace dampers and any other gas-burning

appliances to their previous condition of use.

7.

Any improper operation of the common venting

system should be corrected. The installation

should conform with the National Fuel Gas

Code, ANSI Z223.1. When resizing any portion

of the common venting system, the system

should be sized to approach the minimum

practical size. Refer to the tables in Appendix G

in the National Fuel Gas Code, ANSI Z223.1. (In

Canada, at the time the boiler is removed from

the common venting system, the common

venting system should be resized. The

installation should conform to CAN/CGA

B149.1 or .2.)

2F. Water Flow System

2F-1. Reversible Water Connections
NOTE:
This procedure is not recommended for

the PH pump-mounted models.

Laars ships the HH boiler with the water

connections on the right side. The HH boiler can be

installed with the water connections on either side. It

could be necessary, or helpful, to switch the

connections to the left side to improve access for

installation service. Perform this modification before

installing the boiler using the following procedures:
1.

Remove the front door.

2.

If there is a vent cap or drafthood installed, it

must be removed before removing the grate top

assembly. On indoor installations (models 175-

250), the drafthood switch must be disconnected

at the vent damper receptacle on the left side of

the boiler.

3.

If the unit is in the low-profile outdoor

configuration, remove the hex-head screws (see

Figure 16) and lift the top assembly straight up.

4.

Remove the screws that fastens the flue collector

hold-down clamps and remove the clamps (see

Figure 17).

Advertising