Figure 12. Standard Base for Combustible Floor.

Figure 13. Typical Roof Mounting with Standard
Combustible Mount Base.

4 ft.

(1.2 m)

4 ft.

(1.2 m)

4 ft.

(1.2 m)

There must be a minimum of 4 feet (1.2 m)

horizontally between the boiler and any door, window,

or gravity inlet to a building (see Figure 11). Also, the

horizontal clearance should be maintained from any

electric meters, gas meters, regulators, or relief

equipment.

If the boiler is installed close to a structure,

protect it from rain water runoff with rain gutters on

the roof or other measures. Do not locate the boiler

near sprinkler systems that could spray water on it.

Avoid locations where wind deflection off

nearby structures might cause wind loading and

downdraft conditions. Where downdraft conditions

exist, locate the boiler at least 3 feet (0.9 m) from the

structure.

2C-3. Flooring - Typical Installation
All boilers are equipped with a special base, as a

standard part of the boiler. The unit is designed and

certified for installation on combustible flooring.

Never install the boiler on carpeting. Never store

objects on or around the base of the boiler.

For rooftop installation, see Figure 12 through

Figure 14.

The boiler must be isolated or otherwise

protected from any source of corrosive chemical

fumes, such as trichlorethylene, perchlorethylene,

chlorine, etc. Install the boiler so that the gas ignition

system components are protected from water

(drippings, spraying, rain, etc.) during operation and

service. Locate the boiler on a waterproof floor with a

floor drain and a 6 inch (152 mm) minimum curb on

all four sides to protect the building if boiler repairs

are needed.

2C-2. Outdoor Installation (U.S. Only)

Caution

Outdoor installations are not recommended in
areas where the danger of snow blockage exists.
HH-PH boilers can be installed in the “low-profile,”
grate top configuration as received from the factory,
or with an optional vent cap/stack.

Locate the boiler in an open, unroofed area. Do

not locate the boiler below or adjacent to any doors,

windows, louvers, grills, etc., which connect in any

way with an inhabited area of a building, even though

the access might be through another structure such as

a garage or utility room (see Figure 10 and Table 1).

Figure 10. Incorrect Outdoor Installation.

Figure 11. Outdoor Location.

WINDOW
OR GRILL

INDOOR
ROOM