LAARS Mighty Therm HH-PH (Sizes 175-400) - Installation, Operation and Maintenance Instructions User Manual

Page 20

Advertising
background image

LAARS HEATING SYSTEMS

Page 20

Figure 31. Flame Patterns.

MAIN BURNER FLAME PATTERN

PILOT FLAME PATTERN

ELECTRONIC PILOT

STANDING PILOT

temperature drop in the system. Set the hi-limit switch

15°F (8°C) above the supply temperature to the

system.

3B. Start-Up Procedure

Lighting instructions can be found on the inside

of the boiler. To start up the boiler:
1.

Make sure the system pump is running and there

is water flow.

2.

Remove the control access panel (front door).

3.

Set the temperature control (see Figure 30) to its

lowest setting.

4.

Turn electric power to the boiler OFF.

5.

Turn the manual gas valve OFF.

6.

Wait 5 minutes to clear out any gas, then smell

for gas. Be sure to smell next to the floor because

some gas is heavier than air and will settle on the

floor.

7.

Turn the manual gas valve ON. (For a standing

or continuous pilot system, follow the lighting

and shutdown instructions.)

8.

Reset all safety devices - high limit, low water

cutoff, etc.

9.

Set the temperature control to the desired setting

(see Figure 30 and section 3A).

10. Replace the control access panel.
11. Turn the electric power to the heater ON.

Caution

On a boiler equipped with the vent damper device,
the damper must be in the open position when the
main burners are operating.

If the boiler will not operate:
a.

Turn off all manual gas supply valves.

b.

Turn the main electrical switch OFF.

c.

Turn the gas to the boiler OFF. Follow the

instructions found on the inside of the boiler and

call a qualified professional technician or gas

supplier.

3C. Adjustment for Minimum Input Rate

(Models with Modulating Gas Valve)

Adjust the red knob on the modulating gas valve

to the dial number for the desired water temperature

(see Table 6). Adjusting the red knob to number “1”

sets the gas flow rate to minimum. The control is

factory set at “5” which is satisfactory for most

installations.

Temp.

Dial No.

°F

°C

1

140

60

2

152

67

3

165

74

4

177

81

5

190

88

6

202

94

7

215

102

8

227

108

9

240

116

Table 6. Modulating Valve Temperature Setting.

3D. Hi-Limit Switch Checkout

After running the boiler for a long enough

period, bring the water temperature within the range of

the hi-limit switch and slowly back off the hi-limit

setting until the boiler shuts off. The main burners

should re-ignite when the hi-limit switch is reset and

turned back up to its original setting. The boiler

should now run until it shuts off automatically on

operating control.

When all the safety shut-off devices have been

tested, refer to Section 3A for the proper settings of

the temperature controls.

Advertising