LAARS Mighty Therm2 MT2V (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 14

Advertising
background image

LAARS Heating Systems

Page 14

SECTION 4A.

Water Connections — Boiler

4A.1 Heating System Piping:

Hot Supply Connections — Boiler

NOTE: This appliance must be installed in a closed

pressure system with a minimum of 12 psi (82.7kPa)

static pressure at the boiler.

Hot water piping should be supported by suitable

hangers or floor stands. Do not support piping with

this appliance. Due to expansion and contraction of

copper pipe, consideration should be given to the type

of hangers used. Rigid hangers may transmit noise

through the system resulting from the piping sliding in

the hangers. It is recommended that padding be used

when rigid hangers are installed. Maintain 1" clearance

to combustibles for hot water pipes.

Pipe the discharge of the relief valve (full size)

to a drain or in a manner to prevent injury in the event

of pressure relief. Install an air purger, an air vent, a

diaphragm-type expansion tank, and a hydronic flow

check in the system supply loop. Minimum fill pressure

must be 12psig (82.7kPa). Install shutoff valves where

required by code.

Suggested piping diagrams are shown (see

Figures

6 through 10

). These diagrams are meant only as a guide.

Components required by local codes must be properly

installed.

4A.2 Cold Water Make-Up — Boiler

1. Connect the cold water supply to the inlet

connection of an automatic fill valve.

2. Install a suitable back flow preventer between the

automatic fill valve and the cold water supply.

3. Install shut off valves where required.

NOTE: The boiler, when used in connection with a

refrigeration system, must be installed so the chilled

medium is piped in parallel with the boiler with

appropriate valves to prevent the chilled medium from

entering the boiler.

The boiler piping system of a hot water heating

boiler connected to heating coils located in air handling

appliances where they may be exposed to refrigerated air

circulation must be equipped with flow control valves or

other automatic means to prevent gravity circulation of

the boiler water during the cooling cycle.

A boiler installed above radiation level, or as

required by the authority having jurisdiction, must be

provided with a low water cutoff device either as a part

of the boiler or at the time of boiler installation.

4A.3 Water Flow Requirements — Boiler

A hydronic heating (closed loop) application

re-circulates the same fluid in the piping system. As a

result, no new minerals or oxygen is introduced into the

system. To ensure a proper operating temperature leading

to long boiler life, a flow rate has been established based

on the fluid temperature rise for this specific size boiler.

Pump-mounted boilers can be ordered for use in

primary secondary piping systems. The pumps used are

sized for the headloss through the heater, plus 30 feet

(9.1m) of full-sized piping (same size as boiler outlet)

and a normal number of fittings.

Table 8

specifies water flow rates for boilers, which

will enable the user to size a pump. The headloss shown

is for the heater only, and the user will need to add the

headloss of the system piping to properly size the pump.

The minimum inlet water temperature for the

Mighty Therm2 is 120°F (49°C) to avoid condensing on

the copper coils.

4A.4 Freeze Protection — Boiler

Boiler installations are not recommended in

areas where the danger of freezing exists unless proper

precautions are made for freeze protection. A non toxic,

heating system, anti-freeze may be added to the hydronic

system provided that the concentration does not exceed

50% and the anti freeze contains an anti foamant.

When a 50/50 mixture is used, increase the water

flow requirements by 15%, and increase the headloss

requirements by 20%.

Power outage, interruption of gas supply, failure

of system components, activation of safety devices, etc.,

may prevent a boiler from firing. Any time a boiler is

subjected to freezing conditions, and the boiler is not

able to fire, and/or the water is not able to circulate,

there is a risk of freezing in the boiler or in the pipes in

the system. When water freezes, it expands. This can

result in bursting of pipes in the system, or damage to

the boiler, which could result in leaking or flooding

conditions.

IMPORTANT NOTES: Different glycol products may

provide varying degrees of protection. Glycol products

must be maintained properly in a heating system,

or they may become ineffective. Consult the glycol

specifications, or the glycol manufacturer, for information

about specific products, maintenance of solutions, and

set up according to your particular conditions.

SECTION 4B.

Water Connections —

Water Heaters

4B.1 Water System Piping —

Water Heater

Hot water piping should be supported by suitable

hangers or floor stands. Do not support piping with this

appliance. Due to expansion and contraction of copper

pipe, consideration should be given to the type of

hangers used. Rigid hangers may transmit noise through

the system resulting from the piping sliding in the

hangers. It is recommended that padding be used when

rigid hangers are installed.

Advertising
This manual is related to the following products: