LAARS Mighty Therm2 MT2V (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 7

Advertising
background image

Mighty Therm

2

Page 7

1.7 Locating Pump-Mounted Boiler with

Respect to Return/Supply Header

For the best results, a pump-mounted Mighty

Therm2 Boiler should be located within 15 feet (4.6m)

of the supply and return headers. The pump is sized for

30 feet (9.1m) of piping.

If the appliance must be installed with longer

piping runs, then larger diameter tubing shall be used.

Consult the factory for assistance.

1.8 Locating Appliance for Correct

Horizontal Vent/Ducted Air Distance

from Outside Wall

The forced draft combustion air blower/blowers

in the appliance has/have sufficient power to pull air

and vent properly when the following guidelines for

horizontal air and vent are followed (

see Table 2

).

NOTE: The vent collar size is larger than the size of

the vent pipe that can be used. Vent collar size and

horizontal pipe diameters can be found in

Table 2

. The

larger vent collar size is to accommodate Category I

(vertical) vent systems.
NOTE: When located on the same wall, the Mighty

Therm2 combustion air intake terminal must be installed

a minimum of 12" (30cm) below the exhaust vent

terminal and separated by a minimum of 36 inches

(91cm) horizontally.

The air intake terminal must be installed high

enough to avoid blockage from snow, leaves and other

debris.

SECTION 2.

Venting and Combustion Air

2.1 Combustion Air

Mighty Therm2 boilers and water heaters must

have provisions for combustion and ventilation air

in accordance with section 5.3, Air for Combustion

and Ventilation, of the National Fuel Gas Code, ANSI

Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1,

Installation Codes, or applicable provisions of the local

building codes.

A Mighty Therm2 appliance may receive

combustion air from the space in which it is installed,

or it can be ducted directly to the unit from the outside.

Ventilation air must be provided in either case.

2.1.1 Combustion Air From Room

In the United States, the most common

requirements specify that the space shall communicate

with the outdoors in accordance with method 1 or 2,

which follow. Where ducts are used, they shall be of the

same cross-sectional area as the free area of the openings

to which they connect.

Method 1: Two permanent openings, one

commencing within 12 inches (30 cm) of the top and one

commencing within 12 inches (30 cm) of the bottom,

of the enclosure shall be provided. The openings shall

communicate directly, or by ducts, with the outdoors

or spaces that freely communicate with the outdoors.

When directly communicating with the outdoors, or

when communicating to the outdoors through vertical

ducts, each opening shall have a minimum free area of

1 square inch per 4000 BTU/hr (5.5 square cm/kW) of

total input rating of all equipment in the enclosure. When

communicating to the outdoors through horizontal ducts,

each opening shall have a minimum free area of not less

than 1 square inch per 2000 BTU/hr (11 square cm/kW)

of total input rating of all equipment in the enclosure.

Table 3

shows data for this sizing method, for each

Mighty Therm2 model.

Method 2: One permanent opening, commencing

within 12 inches (30 cm) of the top of the enclosure,

shall be permitted. The opening shall directly

communicate with the outdoors or shall communicate

through a vertical or horizontal duct to the outdoors or

spaces that directly communicate with the outdoors and

shall have a minimum free area of 1 square inch per

3000 BTU/hr (7 square cm/kW) of the total input rating

of all equipment located in the enclosure. This opening

must not be less than the sum of the areas of all vent

connectors in the confined space.

Other methods of introducing combustion and

ventilation air are acceptable, providing they conform to

the requirements in the applicable codes listed above.

In Canada, consult local building and safety codes

or, in absence of such requirements, follow CSA B149.1.

2.1.2 Intake Combustion Air

The combustion air can be taken through the

wall, or through the roof. When taken from the wall, it

must be taken from out-of-doors by means of the Laars

horizontal wall terminal (

see Table 2

). When taken

from the roof, a field-supplied rain cap or an elbow

arrangement must be used to prevent entry of rain water

UNIT

EACH OPENING*

SIZE

SqUARE INCHES

SqUARE CM

500

125

807

750

188

1213

1000

250

1613

1250

313

2020

1500

375

2420

1750

438

2826

2000

500

3226

*Net Free Area in Square Inches / Square cm

Area indicated is for one of two openings; one at floor level and one

at the ceiling, so the total net free area could be double the figures

indicated.
This chart is for use when communicating directly with the

outdoors. For special conditions and alternate methods, refer to the

latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of

louvers. Correct for screen resistance to the net free area if a

screen is installed. Check all local codes applicable to combustion air.

Table 3. Combustion Air Openings.

Advertising
This manual is related to the following products: