LAARS Mighty Therm2 MT2V (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 21

Advertising
background image

Mighty Therm

2

Page 21

5.1.1 Changing Single Circuit to Two

Circuits

Sizes 500 to 1500 will be shipped from the factory

for a single 120-volt power supply. To use a separate

circuit for the pump:

1. Ensure power is disabled to the unit.

2. Remove the three jumper wires that connect the

L2, N2 and GROUND wires on terminal block 1

to the main distribution terminal block. These

wires will be black/white, white and green

respectively.

5.2 Field Wiring

Main Power: The main field wiring connection

points are located inside the line voltage connection/

WARNING

The appliance must be electrically grounded in

accordance with the requirements of the authority having

jurisdiction or, in the absence of such requirements, with

the latest edition of the National Electrical Code, ANSI/

NFPA 70, in the U.S. and with latest edition of CSA

C22.1 Canadian Electrical Code, Part 1, in Canada. Do

not rely on the gas or water piping to ground the metal

parts of the boiler. Plastic pipe or dielectric unions may

isolate the boiler electrically. Service and maintenance

personnel, who work on or around the boiler, may be

standing on wet floors and could be electrocuted by an

ungrounded boiler.

Single pole switches, including those of safety

controls and protective devices must not be wired in a

grounded line.

All electrical connections are made in the field

wiring terminal strip, which is located at the right side of

the appliance.

NOTE: All internal electrical components have been pre-

wired. No attempt should be made to connect electrical

wires to any other location except the wiring box.

5.1 Main Power

All Mighty Therm2 non-pump-mounted heaters

require a single 120-volt fused supply. See

Figure 15

for

over current protection ratings.

Pump-mounted Mighty Therm2 models 500 to

1500 use a single 120-volt fused supply. The installer

can change these units to use a separate circuit for the

pump, if desired. Instructions to make this change are

found in

Section 5.1.1.

Pump-mounted Mighty Therm2 models 1750

and 2000 require two 120-volt fused supplies. See

Figure

15

for over current protection ratings.

Figure 16. Mighty Therm2 (500–750) Wiring Diagram.

Figure 15. Field Wiring.

SINGLE CIRCUIT CONN.

PUMP PUMP

SIZE

HEATER

ONLY ONLY

W/O PUMP

W / PUMP

TACO

B&G

500

15

20

15

15

750

15

20

15

15

1000

20 (TACO) 25 / 30 (B&G) 15

15

1250

25

30

15

15

1500

25

30

15

15

1750

25

15

20

2000

25

20

20