LAARS Mighty Therm2 MT2V (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 20

Advertising
background image

LAARS Heating Systems

Page 20

Figure 14. Water Heater Piping — Multiple Heaters, Multiple Tanks.

Table 9. Water Flow Requirements — MT2V.

Unit

gpm

ft

Temp Rise °F

lpm

m

Temp Rise °C

Size

S

N

H

S

N

H

S N H

S N H

S N H

S N H

500

45

68

90

1.8

2.3

3.5

19 13 9

170 257 341 0.5 0.7 1.1

10 7 5

750

45

68

90

2.1

3.0

6.0

28 19 14

170 257 341 0.6 0.9 1.8

16 10 8

1000

45

68

90

2.3

3.6

6.1

38 25 19

170 257 341 0.6 1.1 1.9

21 14 10

1250

68

68

90

3.8

3.8

6.3

31 31 24

257 257 341 1.2 1.2 1.9

17 17 13

1500

68

68

90

3.9

3.9

6.5

38 38 28

257 257 341 1.2 1.2 2.0

21 21 16

1750

68

68

90

4.0

4.0

6.7

44 44 33

257 257 341 1.2 1.2 2.0

24 24 18

2000

112 112 112

10.0 10.0 10.0

30 30 30

424 424 424 3.0 3.0 3.0

17 17 17

NOTES: S = soft water (1 to 7.5 grains hardness).

N = normal water (7.6 to 17 grains hardness).

H = hard water (more than 17 grains hardness).

gpm = gallons per minute; lpm = liters per minute; ft = headloss in feet; m = headloss in meters.

Headloss is for heater's heat exchanger only.