LAARS Mighty Therm2 MT2V (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 28

Advertising
background image

LAARS Heating Systems

Page 28

as long as the unit is being called for heat. The

blower and pump come on for pre-purge, then

the ignitor warm-up sequence starts and after the

ignitor warm-up is complete and all safety devices

are verified, the gas valves open. If ignition doesn’t

occur, check that there is proper gas supply. Wait

5 minutes and start the unit again. During initial

start up, air in the gas line may cause the Mighty

Therm2 to "lock out" during the first few trials

for ignition. Depending on the ignition modules

installed, the manual reset button on the ignition

modules may need to be depressed to restart the

Mighty Therm2.

6. When the unit is running, the supply gas pressure

must be checked. Inlet gas pressure must not

exceed 13" W.C. (3.2kPa). The minimum inlet gas

pressure is 5" W.C. (1.2kPa).

7. Once the inlet gas pressure is verified, the

outlet gas pressure from each valve (manifold

gas pressure) must be checked, and adjusted, if

necessary. The manifold gas pressure must be 2.5"

W.C. (0.62kPa).

8. Complete the setup by checking the CO

2

at the

outlet of the unit. The CO

2

should be 8% for natural

gas, or 9.2% for propane.

9. After placing the appliance in operation, the

Burner Safety Shutoff Device must be tested.

(a) Close gas shutoff valve with burner operating.

(b) The flame will go out and blower will

continue to run for the post purge cycle.

One additional attempt to light will follow.

Ignition will not occur as the gas is off. The

ignition control will lockout, and will have to

be reset before the unit will operate.

(c) Open gas shutoff valve. Restart the appliance.

The ignition sequence will start again and the

burner will start. The appliance will return to

its previous mode of operation.

NOTE: Unit sizes 1000–2000 have two ignition controls

and two ignitors, which work independently of one

another. If the ignition control for stage 1 fails to properly

light the main burners for that stage, the second ignition

control will still be active, and will be able to energize

stage 2. This, of course, will only occur upon call for

stage 2 and if all other safety devices confirm that the

unit will run in a safe condition.

6.6.2 High Altitude Adjustment and Set Up

Mighty Therm2 appliances may be operated at

high altitude (7700 ft., 2347 m) with a reduction in

output of approximately 10%. At altitudes of less than or

more than 7700 ft. (2347 m) the appliance will perform

equally as well, but with differing reductions in output.

At elevations higher than 7700 ft. (2347 m) the reduction

in output will exceed 10% and at elevations below 7700

ft. (2347 m) it will be less than 10%. High altitude

adjustment must not be made on appliances operating at

elevations below 2500 ft. (762 m).

and to replace any part of the control system and any

gas control that may have been

under water.

6.3 Operating Temperature Control

All Mighty Therm2's are equipped with a two-stage

aquastat. To utilize this mounted controller be sure to

have the "Local/Remote" selector switch to "Local".

Set the controller to the desired operating set point.

The controller has an interstage differential that can be

adjusted from 3°F to 10°F. This allows the user to have

some control over how stage 2 and stage 1 call for heat

(

see Figure 22

).

Because the Mighty Therm2 controller senses inlet

water and the manual reset high limit senses outlet water,

the high limit should be set 40-50°F higher than the

controller, to avoid nuisance lockout of the manual reset

high limit.

6.4 External Boiler Operations

If controlling the stages of the MT2 from an

external source (multiple boiler control, BAS, etc) the

"Local/Remote" selector switch above the terminal strip

must be placed in the "Remote" position. In this mode,

the controller that is mounted on the MT2 will no longer

have control of the unit. The 24V from the unit waits at

the input terminal, and the external control switches this

24V from the input terminal to the stage terminal.

6.5 Limit Controls

The manual reset high limit control is provided

as standard equipment on all heaters. An additional

automatic reset switch is optional.A high limit

temperature-sensing bulb is always located in the heater

outlet. Burners will automatically shut down whenever

overheating occurs.

6.6 Operating the Burner and Set Up

6.6.1 Set Up for 0 to 2500 Feet Altitude

The Mighty Therm2 appliance utilizes a modular

design to achieve its stage-firing. The setup must be

checked before the unit is put in operation. Problems

such as failure to start, rough ignition, strong exhaust

odors, etc. can be due to improper setup. Damage to the

Mighty Therm2 resulting from improper setup is not

covered by the limited warranty.

1. Using this manual, make sure the installation

is complete and fully in compliance with the

instructions.

2. Determine that the appliance and system are filled

with water and all air has been bled from both.

Open all valves.

3. Observe all warnings on the Operating Instructions

label and turn on gas and electrical power to

appliance.

4. Switch on the appliance power switch located on

the right side of the unit.

5. The Mighty Therm2 will enter the start sequence,

Advertising
This manual is related to the following products: