Page 4

1.2 Model Identification

Consult the rating plate on the unit. The following

information describes the model number structure.

1-3 Model Series Designation

M T 2 = Mighty Therm2

4 Usage

H = Hydronic

V = Volume Water

5-8 Size

0 5 0 0 = 500,000 BTU/h input

0 7 5 0 = 750,000 BTU/h input

1 0 0 0 = 999,000 BTU/h input

1 2 5 0 = 1,250,000 BTU/h input

1 5 0 0 = 1,500,000 BTU/h input

1 7 5 0 = 1,750,000 BTU/h input

2 0 0 0 = 1,999,000 BTU/h input

9 Fuel

N = Natural Gas

P = Propane

10 Altitude

A = 0–10,000 feet

11 Location

C = Indoor and Outdoor

12 Firing Mode

K = Two-stage

13 Revision

1 = First version of design

14 Heat Exchanger

B = Glass-lined cast iron / copper / bronze trim

(std. on water heaters)

C = Glass-lined cast iron / copper

(std. on boilers, n/a on water heaters)

N = Glass-lined cast iron / cupro-nickel

(n/a on water heaters)

P = Glass-lined cast iron / cu-nickel / bronze trim

15 Option Code

X = Standard unit

J = CSD-1, FM, IRI, IL

16 Pump Options

X = No Pump

H = Pump mounted MT2V, TACO, hard water pump

N = Pump mounted (any), TACO, normal water pump

S = Pump mounted MT2V, TACO, soft water pump

C = Pump mounted MT2V, B&G, hard water pump

B = Pump mounted (any), B&G, normal water pump

D = Pump mounted MT2V, B&G, soft water pump

1.3 Warranty

Laars Heating Systems appliances are covered by a

limited warranty. Owners should submit online warranty

registration at

www.Laars.com

.

All warranty claims must be made to an authorized

Laars Heating Systems representative, directly to

Customer Service, or online at

www.Laars.com

. Claims

must include the serial number and model number (this

information can be found on the rating plate), installation

date, and name of the installer. Shipping costs are not

included in the warranty coverage.

Some accessory items are shipped in separate

packages. Verify receipt of all packages listed on the

packing slip. Inspect everything for damage immediately

upon delivery, and advise the carrier of any shortages

or damage. Any such claims should be filed with the

carrier. The carrier, not the shipper, is responsible for

shortages and damage to the shipment whether visible or

concealed.

1.4 Dimensions

See Figures 1 and 2.

1.5 Locating the Appliance

The appliance should be located to provide

clearances on all sides for maintenance and inspection.

It should not be located in an area where leakage of any

connections will result in damage to the area adjacent to

the appliance or to lower floors of the structure.

When such a location is not available, it is

recommended that a suitable drain pan, adequately

drained, be installed under the appliance.

The appliance is design certified by CSA-

International for installation on combustible flooring;

in basements; in closets, utility rooms or alcoves.

Mighty Therm2 Boilers or Water Heaters must

never be installed on carpeting. The location for the

appliance should be chosen with regard to the vent

pipe lengths and external plumbing. The unit shall be

installed such that the gas ignition system components

are protected from water (dripping, spraying, rain, etc.)

during operation and service (circulator replacement,

control replacement, etc.). When vented vertically, the

Mighty Therm2 must be located as close as practical

to a chimney or outside wall. If the vent terminal and/

REqUIRED

RECOMMENDED

APPLIANCE

CLEARANCE FROM

SERVICE ACCESS

SURFACE

COMBUSTIBLE MATERIAL

CLEARANCE

inches

cm inches

cm

Left Side

1

2.5 24

61

Right Side

1

2.5 24

61

Top

1 2.5 12 30

Back

1

2.5

**

12**

30**

Front

1

2.5

36

91

Vertical

(Category 1)

6*

15.2*

Vent

Horizontal

per UL1738 venting

(Category 3)

system supplier’s

Vent

instructions

*1" (2.5cm) when b-vent is used.

**When vent and/or combustion air connects to the back,
recommended clearance is 36" (91cm).