LAARS Pennant PNCP - Install and Operating Manual User Manual

Page 15

Advertising
background image

Pennant Pool Heater

Page 15

changing the dLS parameter. After scrolling through

the parameters until dLS is displayed, press the enter

button. The setpoint will be displayed. Press the up

arrow or down arrow buttons until the desired setpoint

is displayed. Press the enter button and the setpoint

will be activated. The display will return to indicating

the present pool loop temperature.

The boiler operating temperature is set by

changing the bsp parameter. After scrolling through

the parameters until bsp is displayed, press the enter

button. The setpoint will be displayed. Press the up

arrow or down arrow buttons until the desired setpoint

is displayed. Press the enter button and the setpoint

will be activated. The display will then return to

indicating the pool loop temperature.

SINGLE

TWO CIRCUIT

SIZE

CIRCUIT

HEATER PUMP

500

20

15

15

750

20

15

15

1000

(TACO) 20 / (B&G) 30 20

15

1250

30

25

15

1500

30

25

15

1750

25

20

2000

25

20

Table 8. Electrical Data (Amps).

Figure 9. Typical Control Panel.

Figure 8. Pool Heater Controller.

The last parameter that may be adjusted is Pd,

the pump off delay. After again scrolling through the

parameters until Pd is displayed, press the enter button.

The pump delay time will be displayed. The pump off

delay may be set between 0.1 and 10 minutes. Press

the up arrow or down arrow buttons until the desired

setpoint is displayed. Press the enter button and the

setpoint will be activated. The display will again return

to indicating the present pool loop temperature.

By depressing the upper left hand button at

any time during the programming, the menu may be

returned to the beginning.

5.3.3 Setpoint - LSP

The setpoint is the desired temperature around

which the heater will control (desired pool temp-

erature). It is adjustable between 60° F and 104° F.