3 warranty, 4 dimensions, 5 locating the appliance – LAARS Pennant PNCP - Install and Operating Manual User Manual

Page 4

Advertising
background image

LAARS Heating Systems

Page 4

14 Heat Exchanger

B = Glass-lined CI / copper / brz trim (std. PNCP)

P = Glass-lined cast iron / cu-nickel / brz trim

15 Option Code

X = Standard unit

J = CSD-1, FM, IRI, IL

16 Pump Options

N = Pump mounted, TACO, normal water pump

B = Pump mounted, B&G, optional normal water pump

1.3 Warranty

Laars Heating Systems appliances are covered

by a limited warranty. Owners should submit online

warranty registration at

www.Laars.com

.

All warranty claims must be made to an authorized

Laars Heating Systems representative, directly to

Customer Service, or online at

www.Laars.com

.

Claims must include the serial number and model

(this information can be found on the rating plate),

installation date, and name of the installer. Shipping

costs are not included in the warranty coverage.

Some accessory items are shipped in separate

packages. Verify receipt of all packages listed on

the packing slip. Inspect everything for damage

immediately upon delivery, and advise the carrier of

any shortages or damage. Any such claims should be

filed with the carrier. The carrier, not the shipper, is

responsible for shortages and damage to the shipment

whether visible or concealed.

1.4 Dimensions

(See Figure 1.)

1.5 Locating the Appliance

The appliance should be located to provide

clearances on all sides for maintenance and inspection.

It should not be located in an area where leakage of

any connections will result in damage to the area

adjacent to the appliance or to lower floors of the

structure.

When such a location is not available, it is

recommended that a suitable drain pan, adequately

drained, be installed under the appliance.

The appliance is design certified by CSA-

International for installation on combustible flooring;

in basements; in closets, utility rooms or alcoves.

The location for the appliance should be chosen

with regard to the vent pipe lengths and external

plumbing. The unit shall be installed such that the gas

ignition system components are protected from water

(dripping, spraying, rain, etc.) during operation and

service (circulator replacement, control replacement,

etc.). When vented vertically, the Pennant must

be located as close as practical to a chimney or

outside wall. If the vent terminal and/or combustion

air terminal terminate through a wall, and there is

potential for snow accumulation in the local area, both

terminals should be installed at an appropriate level

above grade.

The dimensions and requirements that are shown

in Table 2 should be met when choosing the locations

for the appliance.

HORIZONTAL

AIR COLLAR

HEATER

VENT COLLAR

VENT PIPE

& PIPE

MAX. PIPE

MAX. NO.

SIDE WALL

SIDE WALL

SIZE

SIZE

DIAMETER*

DIAMETER

LENGTH

OF ELBOWS

VENT

COMBUSTION

TERMINAL

AIR

TERMINAL

IN. CM IN.

CM IN

CM FT.

M

PART NUMBER

PART NUMBER

500

8 20 6

15 6

15 50

15

3

CA001401 20260701

750 10 25 8

20 6

15 50

15

3

CA001402 20260701

1000 10 25 8

20 8

20 50

15

3

CA001402 20260703

1250 12 30 8

20 8

20

50 15

3

CA001403

20260703

1500 12 30 8

20 8

20 50

15

3

CA001403 20260703

1750 14 36

8 20 8

20

50 15

3

CA001405

20260703

2000 14 36 12

30

12 30 50

15

3

CA001404 20260706

*Horizontal venting requires stainless vent pipe. See Table 5.

Table 1. Horizontal Vent / Combustion Air Parameters.