LAARS Pennant PNCP - Install and Operating Manual User Manual

Page 7

Advertising
background image

Pennant Pool Heater

Page 7

Figure 2. Combustion Air and Vent Through Roof.

TERM DESCRIPTION

Pipe Single-wall galvanized steel pipe, 24 gauge

minimum (either insulated or non-insulated)

Joint

Permanent duct tape or aluminum tape

Sealing

Table 4. Required Combustion Air Piping Material.

Btu/hr (5.5 square cm/kW) of total input rating of all

equipment in the enclosure. When communicating to

the outdoors through horizontal ducts, each opening

shall have a minimum free area of not less than

1 square inch per 2000 Btu/hr (11 square cm/kW) of

total input rating of all equipment in the enclosure.

Table 3 shows data for this sizing method, for each

Pennant model.

Method 2: One permanent opening, commencing

within 12 inches (30 cm) of the top of the enclosure,

shall be permitted. The opening shall directly

communicate with the outdoors or shall communicate

through a vertical or horizontal duct to the outdoors

or spaces that directly communicate with the outdoors

and shall have a minimum free area of 1 square inch

per 3000 Btu/hr (7 square cm/kW) of the total input

rating of all equipment located in the enclosure. This

opening must not be less than the sum of the areas of

all vent connectors in the confined space.

Other methods of introducing combustion and

ventilation air are acceptable, providing they conform

to the requirements in the applicable codes listed

above.

In Canada, consult local building and safety

codes or, in absence of such requirements, follow

CAN/CGA B149.

2.1.2 Intake Combustion Air

Never obtain combustion air from the pool area.

Corrosion of and/or damage to the pool heater may

result. The combustion air can be taken through the

wall, or through the roof. When taken from the wall, it

must be taken from out-of-doors by means of the Laars

horizontal wall terminal (see Table 1). When taken

from the roof, a field-supplied rain cap or an elbow

arrangement must be used to prevent entry of rain

water (see Figure 2).

Use single-wall galvanized pipe, per table

4, for the combustion air intake (see Table 1 for

appropriate size). Route the intake to the heater as

directly as possible. Seal all joints with tape. Provide

adequate hangers. The unit must not support the

weight of the combustion air intake pipe. Maximum

linear pipe length allowed is 50 feet (15.2m). Three

elbows have been calculated into the 50-foot (15.2m)

linear run. Subtract 10 allowable linear feet (3.0m) for

every additional elbow used (see Table 1). When fewer

than 3 elbows are used, the maximum linear pipe

length allowed is still 50 feet (15.2m).

The connection for the intake air pipe is on the

filter box. The Pennant appliances may have venting

and combustion air ducting attached to the top or the

back. They are shipped with the connections at the

top. For attaching either or both pipes to the back,

the mounting flanges are reversible by removing the

mounting screws and orienting the flanges in the

desired position. Replace the screws after positioning

flanges. Run a bead of silicone around the collar and

slide the pipe over the collar. Secure with sheet metal

screws.

In addition to air needed for combustion, air

shall also be supplied for ventilation, including all air

required for comfort and proper working conditions

for personnel. The Pennant loses less than 1 percent of

its input rating to the room, but other heat sources may

be present.

2.2 Venting

2.2.1 Vent Categories

Depending upon desired Pennant venting, it

may be considered a Category I or a Category III

appliance. In general, a vertical vent system will be

a Category I system. However, in rare instances, a

Pennant’s vertical vent system may be considered

Category III. In the U.S., the National Fuel Gas Code

(American National Standard Z223.1-Latest Edition),

or in Canada the CSA B149.1 (latest edition), defines

a Category I vent system, and includes rules and tables

to size these vent systems. If the Pennant’s vertical

vent system does not satisfy the criteria for Category I

venting, it must be vented as a Category III system.

All Pennant vent systems which discharge

horizontally (without the use of a power venter) are

considered Category III vent systems.

Advertising