LAARS Pennant PNCP - Install and Operating Manual User Manual

Page 23

Advertising
background image

Pennant Pool Heater

Page 23

8.4 High Gas Consumption

Appliances operating with an improper air/

fuel ratio are very inefficient and consequently, have

very high gas consumption. Because efficiency is

high when the CO

2

is high (or O

2

is low), appliances

operating with low CO

2

or high O

2

(especially LP

appliances) consume more gas. Adjust the CO

2

or O

2

for optimum efficiency. If no combustion analyzing

equipment (CO

2

or O

2

) is available then a proper

adjustment of the air/fuel ratio (CO

2

or O

2

) cannot

be accomplished. However, by briefly sniffing the

flue gases it is possible to determine if the CO

2

or

O

2

is within the proper range. No significant flue gas

odor should be detected when combustion is proper.

A strong piercing smell indicates poor combustion

and generally a lean mixture - low CO

2

or high O

2

.

The CO

2

should be 8% (natural gas, 9.2% LP) at high

fire. To check the CO

2

, first verify that the supply gas

pressure is within 5" to 13" w.c. (1.2 to 3.2 kPa) With

the Pennant running with both stages firing, set the

air box pressure to 1.5" w.c. (0.37 kPa) (as a starting

point), by adjusting the air shutter(s) at the bottom of

the fan(s). Check the CO

2

, and adjust the air shutters if

further adjustment to the CO

2

is needed. Sizess 1250,

1500, 1750 and 2000 have two blowers and two air

chambers (boxes). The pressure of each air box must

be equal when the final adjustment is made.

8.5 Troubleshooting the Pool Heater

Temperature Control

With a Voltmeter, test for 24 VAC between

terminals 1 & 2 on the 10 pin connector. Check that

the sensor temperature is lower than the setpoint

temperature by at least the differential setting. If this

is true, check that there is 24 VAC at the yellow wire

on the 4 pin connector. If there is not 24 VAC, check

that the high limit is not open. If there is 24 VAC at the

yellow wire on the 4 pin connector and not at the light

blue wire on that connector, replace the control.

8.6 Troubleshooting Pennant Controls

The Pennant series consists of three sizes with

one ignition module (500, 750 & 1000) and four sizess

with two ignition modules (1250, 1500, 1750 and

2000).

A diagnostic panel, that includes test points, as

well as diagnostic lights, is provided in the control

module. It is located on the right side of the module,

behind the display. To access, remove the retaining

screws from the display cover panel and remove

it. Grasp the control module at its base and pull it

outward. Ladder diagrams are shown in Figures 13 and

14.

Figure 13 shows the diagram for the 500, 750 &

1000. These have one blower and one ignition module.

The blower is energized directly through the “inducer”

terminals F1 and F2 of the (Fenwal) ignition module.

The 24V power to the T’STAT terminal of the ignition

module(s) are routed through the safety interlocks.

The ladder diagram for sizess 1250, 1500, 1750

and 2000 is shown in Figure 14. These models have

two ignition modules, each with its own blower, and

each controlling part of the input so that startup at

reduced input is provided. The blowers are energized

by the ignition modules indirectly via switching relays.

When either ignition module receives a call for heat, it

switches its blower to high speed and the blower of the

idle ignition module to low speed.

The wiring schematic for the Pennant 500 – 1000

is shown in Figure 15, and the schematic for the 1250

– 2000 models is shown in Figures 16 and 17. All

24V wiring is routed through the diagnostic PC board.

Wiring harnesses connect between the diagnostic PC

board and the control components, indicator board,

or field wiring terminal strip. The diagnostic board

contains LEDs that indicate open status of the safety

interlocks, and quick-connect terminals that provide

tests points for checking voltage/continuity at various

points in the control circuit.

Certain control elements that may need to be

rewired in the field are connected via the field wiring

terminal strip rather than to the diagnostic PC board.

These include the low-water cutoff (LWCO), external

alarm, and water flow switch.

SECTION 9.

Replacement Parts

Only genuine Laars replacement parts should be used.

9.1 General Information

To order or purchase parts for the Laars Pennant,

contact your nearest Laars dealer or distributor. If

they cannot supply you with what you need, contact

Customer Service (see back cover for address,

telephone and fax numbers).

9.2 Parts List

See next page.

Advertising