LAARS Pennant PNCP - Install and Operating Manual User Manual

Page 18

Advertising
background image

LAARS Heating Systems

Page 18

HEATER

MINIMUM FILTER

MODEL

PUMP FLOW RATE

PNCP 500

240 GPM

PNCP 750

360 GPM

Table 9. Minimum Filter Pump Flow Rates For Spas.

appliance will return to its previous mode

of operation.

NOTE: Models 1250, 1500, 1750 and 2000 have two

ignition controls and two ignitors.

6.3.2 High Altitude Adjustment and Set Up

Pennant appliances may be operated at high

altitude (7700 ft., 2347 m) with a reduction in output

of approximately 10%. At elevations higher than 7700

ft. (2347 m) the reduction in output will exceed 10%

and at elevations below 7700 ft. (2347 m) it will be

less than 10%. When adjusted properly, the appliance

will perform properly at any altitude. High altitude

adjustment must not be made on appliances operating

at elevations below 2500 ft. (762 m).

No orifice changes are required to adjust the

Pennant appliances for high altitude. High altitude

adjustment is accomplished by adjustment of the gas

valve manifold pressure and the air shutter(s). The

required instruments used to assist in these adjustments

are a CO

2

or O

2

Analyzer and a U-Tube Manometer or

other device capable of reading a pressure of 2.5-3.0

inches W.C. (0.62-0.75 kPa).

Start the adjustment process by checking the CO

2

in the “as installed” condition. Adjust the air shutter(s)

so that the CO

2

is about 8% or the O

2

is about 6.8% for

appliances operating on Natural Gas. For appliances

operating on LP Gas adjust the air shutter(s) so that the

CO

2

is about 9.2% or the O

2

is about 6.8%. Appliances

with two blowers should be adjusted so that the air

shutters below each blower are open the same amount.

Once the CO

2

or O

2

has been set, the manifold

pressure may be adjusted. Remove the 1/8 NPT plug

from the lower side of the gas valve that is to be set

and install a fitting, hose and manometer. Start the

appliance and observe the manifold pressure. Manifold

pressure must be adjusted to 3.0 in. W.C. (0.75 kPa)

(for high altitude only, standard operating pressure is

2.5 in. W.C. (0.62 kPa)). It is adjusted by removing the

slotted cap on the gas valve and turning the adjustment

screw (beneath the cap) clockwise to increase pressure

. After the adjustments have been completed, the fit-

ting, hose and manometer have been removed and the

1/8" plug has been replaced, replace the cap. Repeat

this process until all gas valves have been set. Note:

The pressure can be set only when the appliance is

operating and only when the particular gas valve being

adjusted is energized by a call for heat.

After all of the gas valve manifold pressures

have been set, the CO

2

or O

2

must be reset. CO

2

or O

2

will have changed when the manifold pressure was

adjusted. Open the air shutter(s) to reduce the CO

2

or

O

2

to the values achieved previously.

The procedure is complete when all gas valves

are adjusted to a manifold pressure of 3.0 in. W.C.

(0.75 kPa) and the CO

2

is adjusted to 8.0% for Natural

Gas appliances or 9.2% for LP appliances. When using

an O

2

analyzer, the correct O

2

is 6.8% for both Natural

Gas and LP appliances.

Caution

Should any odor of gas be detected, or if the gas

burner does not appear to be functioning in a

normal manner, close main shutoff valve, do not

shut off switch, and contact your heating contractor,

gas company, or factory representative.

6.4 Shutting Down the Pennant

1. Switch off the shutdown switch (located above

the Main Power Switch).

2. Wait until the “pump” light (located on the front

panel) goes out.

3. Switch off the main electrical disconnect switch.

4. Close all manual gas valves.

5. If freezing is anticipated, drain the Pennant and

be sure to also protect piping connected to the

Pennant from freezing.

This step to be performed by a qualified service person.

6.5 Backwash Switch Operation

Pennant Pool Heaters are equipped with a filter

backwash switch, which is located above the main

power switch. The switch is intended to provide a

means by which the heater can be safely shut down for

pool filter service, without causing nuisance tripping

of the heater high limit.

This switch is internally wired in series with the

Other Interlocks terminals, and will interrupt the call

for heat signal when open. Please note that when the

backwash switch is active the heater “Service” light

will be illuminated.

To place the heater into backwash mode proceed

as follows:

1. Turn the backwash switch down to the “Filter

Backwash Mode” position.

2. Wait for the heater outlet temperature to drop

down to a temperature equal to the pool water

return temperature.

3. Turn the main power switch off.

Pool filter servicing may now proceed normally.

After completion of the filter servicing, place the

heater back into service as follows:

1. Turn the main power switch on.

2. Allow time for the pump to turn on, and purge air

from the heater.

3. Turn the backwash switch up to the “Normal”

position.

Advertising