Pennant

(500-2000)

Page 23

GPM

FT

TEMP RISE °F

LPM

M

TEMP RISE °C

SIZE

S N H S N H S N H S

N

H

S

N

H

S

N

H

500

45 68 90 1.8 2.3 3.5 19 13 9

170 257 341 0.5 0.7 1.1 10 7 5

750

45 68 90 2.1 3.0 6.0 28 19 14

170 257 341 0.6 0.9 1.8 16 10 8

1000

45 68 90 2.3 3.6 6.1 38 25 19

170 257 341 0.6 1.1 1.9 21 14 10

1250

68 68 90 3.8 3.8 6.3 31 31 24

257 257 341 1.2 1.2 1.9 17 17 13

1500

68 68 90 3.9 3.9 6.5 38 38 28

257 257 341 1.2 1.2 2.0 21 21 16

1750

68 68 90 4.0 4.0 6.7 44 44 33

257 257 341 1.2 1.2 2.0 24 24 18

2000

112 112 112 10.0 10.0 10.0 30 30 30

424 424 424 3.0 3.0 3.0 17 17 17

NOTES: 1. S = soft water (1 to 7.5 grains hardness)

2. N = normal water (7.6 to 17 grains hardness)

3. H = hard water (more than 17 grains hardness)

4. gpm = gallons per minutes, lpm = liters per minute, ft = headless in feet, m = headloss in meters

5. Headloss is for heater’s heat exchanger only

Table 9. Water Flow Requirements – PNCV.

Figure 12. Water Heater Piping — Multiple Heaters, Multiple Tanks.