SINGLE CIRCUIT CONNECTIONS

PUMP

HEATER

ONLY

W/O PUMP

WITH PUMP

TACO B&G

500

15

20

15 15

750

15

20

15 15

1000

20

25 (TACO) 30 (B&G) 15 15

1250

25

30

15 15

1500

25

30

15 15

1750

25

15 20

2000

25

20 20

Table 10. Electrical Data.

Figure 13. Removing Jumpers.

SECTION 5.

Electrical Connections

WARNING

The appliance must be electrically grounded in

accordance with the requirements of the authority

having jurisdiction or, in the absence of such

requirements, with the latest edition of the National

Electrical Code, ANSI/NFPA 70, in the U.S. and

with latest edition of CSA C22.1 Canadian Electrical

Code, Part 1, in Canada. Do not rely on the gas

or water piping to ground the metal parts of the

boiler. Plastic pipe or dielectric unions may isolate

the boiler electrically. Service and maintenance

personnel, who work on or around the boiler, may

be standing on wet floors and could be electrocuted

by an ungrounded boiler.

5.1 Main Power

Single pole switches, including those of safety

controls and protective devices must not be wired in a

grounded line.

All electrical connections are made in the field

wiring terminal strip, which is located at the right side

of the appliance.

NOTE: All internal electrical components have been

prewired. No attempt should be made to connect

elec-trical wires to any other location except the wiring

box.

5.1.1 Power Circuits

All Pennant non-pump-mounted heaters require a

single 120-volt fused supply.

Pump-mounted Pennants models 500-1500 also

uses a single 120-volt fused supply and models 1750-

2000 use two 120-volt fused supplies.

The installer can change the pump mounted

single service heaters to use a separate circuit for the

pump, if desired. Instructions to make this change are

found in

Section 5.1.2

.

Pennant 500-1500 main power (L1, N1 &

Ground) shall be connected to the three wires (10

AWG) supplied. Over current protection ratings can be

found in

Table 10.

Pennant 1750-2000 will require two 120-volt

fused supplies. Heater circuit can be identified with

10AWG wires to include black, white and green (all

solid colors). Pump circuit can be identified with three

12AWG wires to include a black wire with a white

tracer (stripe), a white and green wire.

5.1.2 Pump Circuit

Conversion to separate pump circuit will

necessitate removing the three jumpers within

the internal wiring of the 120-volt portion of the

heater (see

Figure 13

). Only do this with the power

disconnected to the unit.

To rewire the pump circuit, bring in another

120-volt fused supply (L2, N2 & Ground). Connect

incoming power (L2) to the main power switch using

spade (fork) terminal. From the other side of the main

power switch connect to the main terminal block using

a ¼" female insulated quick connect. This will be

the same position where the jumper had terminated.

Connect N2 and Ground to the main terminal block

using ¼" female insulated quick connect (refer to

Figure 13

).

Ladder diagrams are shown in

Figures 16

through 18,

while wire diagrams are shown in

Figures

19 through 21.

5.2 Temperature Control

5.2.1 Temperature Control Description

The field wiring panel is located on the right side

of the Pennant (shown in

Figure 14

). The following

components are connected to the field wiring panel:

Temperature sensor: The sensor supplied loose

with the Pennant is installed in the piping or tank,