LAARS Pennant PNCV (Sizes 500-2000) - Install and Operating Manual User Manual

Page 41

Advertising
background image

Pennant

(500-2000)

Page 41

Caution

If the tank temperature control is set too high, a

potential for hot water scalding may exist.

Mode 2: Primary secondary piping.

Install a “supply sensor” in the primary loop

using the Laars part number R2014800 sensor

(included with every Pennant unit). Connect the sensor

to the “S C2” and “SUP S” terminals.

You must provide an indication of the system’s

heat demand by removing the jumper across the

“ComD” and “HtD” terminals on the field wiring

panel and connecting a zone valve or zone pump end

switch, thermostat, aquastat or other contact closure to

these terminals. If the “ComD” and “HtD” terminals

are left jumpered, the control will always see a heat

demand and remain in “Dem” mode, with the boiler

pump running continuously. See

Section 5.2

for more

information.

A secondary aquastat, such as for a separate heat

exchanger for DHW, can be connected to the “Set D”

and “Com D” terminals. A call for heat from these

controls will start the boiler pump and cause the boiler

to fire.

If the boiler is not a pump mounted model, a

24VAC pump contactor may be connected to the

“PMP” terminals to control a field installed pump.

Program the temperature control to use Mode 2.

The

AUTO/MAN

switch must be in the

AUTO

position in

this mode.

Mode 4: Hydronic outdoor reset system

without primary / secondary piping.

Laars strongly suggests the use of primary

secondary piping with the Pennant boiler. This piping

style best ensures that the Pennant will have proper

water flow. However, non-primary secondary methods

can be used successfully, so this section has been

included.

Install the outdoor reset sensor, Laars part

number R2014000, and connect the leads to the “OD

S” and “S C2” terminals.

You must provide an indication of the system’s

heat demand by removing the jumper across the

“ComD” and “HtD” terminals on the field wiring

panel and connecting a zone valve or zone pump end

switch, thermostat, aquastat or other contact closure to

these terminals. If the “ComD” and “HtD” terminals

are left jumpered, the control will always see a heat

demand and remain in “Dem” mode, with the boiler

pump running continuously. See

Section 5.2

for more

information.

Reset Override: An additional thermostat or aquastat

may be connected to the “Set D” and “Com D”

terminals. A call for heat from either of these controls

will start the boiler’s pump and cause the boiler to fire.

If the boiler is not a pump mounted model, a

24VAC pump contactor may be connected to the

“PMP” terminals to control a field installed pump.

Program the temperature control to use Mode 4.

The

AUTO/MAN

switch must be in the

AUTO

position in

this mode.

Mode 5: Primary secondary piping with

outdoor reset.

Install the outdoor reset sensor,

Laars part

number R2014000,

and connect the leads to the “OD

S” and “S C2” terminals. Install a “supply sensor”

in the primary loop using the

Laars part number

R2014800 sensor

(included with every Pennant

unit). Connect the sensor to the “S C2” and “SUP S”

terminals.

You must provide an indication of the system’s

heat demand by removing the jumper across the

“ComD” and “HtD” terminals on the field wiring

panel and connecting a zone valve or zone pump end

switch, thermostat, aquastat or other contact closure to

these terminals. If the “ComD” and “HtD” terminals

are left jumpered, the control will always see a heat

demand and remain in “Dem” mode, with the boiler

pump running continuously. See

Section 5.2

for more

information.

A secondary aquastat, such as for a separate heat

exchanger for DHW, can be connected to the “Set D”

and “Com D” terminals. A call for heat from these

controls will start the boiler pump and cause the boiler

to fire.

If the boiler is not a pump mounted model, a

24VAC pump contactor may be connected to the

“PMP” terminals to control a field installed pump.

Program the temperature control to use Mode 5.

The

AUTO/MAN

switch must be in the

AUTO

position in

this mode.

Mode 6: Boiler with external staging control

(multiple boiler control, building

automation system, energy

management system, etc.)

Leave the jumper installed between “Ht D” and

“Com D” terminals. There are terminals on the field

wiring panel that must be wired per the instructions in

Section 5.3

of this manual. Other wiring methods

may be unsafe. The wiring in

Section 5.3

of this

manual must be used.

The

AUTO/MAN

switch is located on the circuit

board in the slide-out control panel on the front of the

Pennant. This switch is placed in the manual position

(MAN)

when an external control is controlling the

Pennant stages.

Program the temperature control to use Mode

6. Mode 6 tells the Pennant control that an external

staging control is being used.

Advertising
This manual is related to the following products: