LAARS Pennant PNCV (Sizes 500-2000) - Install and Operating Manual User Manual

Page 40

Advertising
background image

LAARS Heating Systems

Page 40

Hydronic Primary/Secondary (Mode 2)

Programming. Mode 2 is used in primary-secondary

piping hydronic systems without outdoor reset. Mode

5 adds outdoor reset.

Step 1: Install the additional sensor in the

primary loop (see

Figure 4

), and wired to the “SC2”

and “SUPS” terminals on the field wiring panel

(Figure 23).

Step 2: Remove the factory-installed jumper

between the “HtD” and “ComD” terminals on the

field wiring panel (

Figure 14

), and connect a zone

valve or pump end switch or other contact closure

device (aquastat, etc.) to these terminals to provide an

indication of heat demand in the system.

Note: The boiler must have an indication of heat

demand to fire. If a zone valve or pump end switch is

not connected to the “HtD” and “ComD” terminals, the

jumper must be left in place. However, the boiler pump

(if equipped) and any pump connected to a contactor

wired to the PMP-PMP terminals on the field wiring

panel will run continuously and not cycle off according

to the setting for the Pump Delay. In addition, the LCD

screen will always show “dem” (demand) and will not

allow cycling of the display to verify all the sensor

settings.

Step 3: Press the three programming buttons

to enter

ADJUST mode (

Figure 25

). Press

Item to

select the programming item, and the

ARROW

keys

to adjust the setting. See

Section 6.3 Programming

the Temperature Control

if more programming

instructions are needed.

Recommended settings for hydronic system with

180°F / 83°C primary loop temperature:

Item F°

MODE 2

2

BOIL TARGET

180

83

BOIL MASS

1

1

DIFF

20

10

DLY 5:00

5:00

°C

Step 4: See

Section 6.4.11 Limit Controls.

Set

both high limit controls at least 25°F / 14°C higher

than the

BOIL TARGET to allow for temperature rise

across the heat exchanger.

6.3.4 Choosing the Mode for your

Application

This section describes various applications and

the recommended field wiring and Mode selections.

Mode 1: Boiler operates using its own inlet

and outlet sensors only, not relying

on a remote thermostat, aquastat,

or external sensor.

This setup is most commonly found in domestic

hot water applications with a continuous run pump.

This is not recommended for other applications.

The Pennant is shipped with a jumper between

the “Com D” and “Ht D” terminals, which must

remain in place to allow the unit to fire. The unit will

fire whenever the outlet temperature cools below the

target temperature.

Important Note: If the Pennant is pump-mounted at

the factory, or if a field-supplied pump contractor is

connected to the Pennant’s pump contactors

(Pmp Pmp), the user

must program the controller’s

pump delay (DLY) setting to ON. When ON is selected,

pump operation is continuous. The unit’s inlet and

outlet sensors must be able to detect the temperature

in the storage tank in order to control it. Without the

tank water continuously running through the heater,

the heater will have no way of knowing what the

temperature in the tank is, and will not be able to

respond to a change in tank temperature. Short cycling

or lack of hot water may result if the pump does not

run continuously.

Mechanical aquastat in a domestic hot

water storage tank.

Remove the jumper from the “Com D” and

“HtD” terminals and connect the aquastat’s leads

to these terminals. This connection uses a standard,

non-powered mechanical aquastat. When the aquastat

calls for heat, the Pennant’s temperature control will

respond and start the boiler pump (if equipped) and

fire the boiler.

If the Pennant is not a pump mounted model,

a 24VAC pump contactor may be connected to the

“PMP” terminals to control a field installed pump.

(If desired, the pump can run continuously, with the

aquastat telling the heater when to fire.)

Program the temperature control to use Mode 1.

The

AUTO/MAN

switch must be in the

AUTO

position in

this mode.

Mode 3: Laars R2014800 sensor installed

in the domestic hot water storage

tank.

The Pennant ships with a jumper between the

“Com D” and “Ht D” terminals. Verify this jumper is

in place, and connect the sensor leads to the “S C2”

and “SUP S” terminals. When the sensor detects a

temperature below the target temperature, the control

will respond and start the heater pump (if equipped)

and fire the heater.

If the heater is not a pump mounted model, a

24VAC pump contactor may be connected to the

“PMP” terminals to control a field installed pump. (If

desired, the pump can run continuously).

Program the temperature control to use Mode 3.

The

AUTO/MAN

switch must be in the

AUTO

position in

this mode.

Advertising
This manual is related to the following products: